BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M349745
Premises: 72 GREENE STREET MANHATTAN BIN: 1079933     Block: 485   Lot: 8
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 72 GREENE ST Census Tract:   49 Health Area:  6800
4TH FLOOR Admin Area:   M - MANHATTAN Inspection Area:   U
NEW YORK, NY 10012 Community Board:   102
Special Place Name:   SIERRA REAL ESTATE
DOB Cross Street(s):   BROOME STREET,    SPRING STREET
Status:   C - JOB IS SIGNED OFF 06/07/2017
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  01/28/2014 7:16 AM
Application Entered:   01/28/2014 Job Start Date:   01/29/2014
Last Change:   06/07/2017 Job End Date:   03/31/2014
Appointment Status:   
Last Inspection By:   RACEWICZ, TOMASZ       On     06/06/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011480 Licensee Name: GREGORY J CARDILLO
Firm: 001965 Firm Name: NEAD ELECTRIC INC.
Firm Phone: 212-764-2752  Firm Address: 530 WEST 50TH STREET NEW YORK NY 10019 

Historical Licensees and Firms:
License # Licensee Name Firm # Firm Name  
012379 TZOULIS, ANGELO 001965 NEAD ELECTRIC INC.

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $219.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   O - Office Bldg
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: ASB 72-76 GREENE ST
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  1  (4)#4(1)#8G
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  24 CIR 100 AMP
D. 3 Phase Over 225 AMPS  1  24 CIR 225 AMP
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
004    20  28    17  31     
Buildings Total 20  28    17  31            
Total Units : 108 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 07/12/2016
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  7276GRG2RK-NEW PANEL & RISER. NEW CIRCUITS, LIGHTS, OUTLETS& NEW MECHANICAL EQUIPMENT.

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M349745
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 07/09/2016 07/12/2016 STP V (60) (8)
INSPECTION COMMENTS: FAIL
 
(2) 10/06/2016 10/07/2016 PHG J Y (30) (0)
INSPECTION COMMENTS: SOME OBJECTIONS REMOVED
 
(3) 06/06/2017 06/07/2017 TOR C R (30) (0)
INSPECTION COMMENTS: OBJECTIONS ONLY

OBJECTION FOR APPLICATION #: M349745
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 3) APPLICATION FOR CERTIFICATE OF ELECTRICAL INSPECTION NOT ON FILE
(FLOOR: 004) MOTORS AND HEATERS NOT FILED FOR
RSLV 07/09/2016 07/09/2016 10/06/2016
 
002 (999) OTHER
(FLOOR: 004) NO TIE HANDLES PANEL RP-4S 210.4
RSLV 07/09/2016 07/09/2016 06/06/2017
 
003 (999) OTHER
(FLOOR: 004) NO ARC FLASH STICKERS 110.16
RSLV 07/09/2016 07/09/2016 10/06/2016
 
004 (999) OTHER
(FLOOR: 004) EMT NEEDS SUPPORT ON CEILING 358.30
RSLV 07/09/2016 07/09/2016 10/06/2016
 
005 (999) OTHER
(FLOOR: 004) NO GFI 6 FT OF SINK 210.8
RSLV 07/09/2016 07/09/2016 10/06/2016
 
006 (999) OTHER
(FLOOR: 004) PANEL RP-4S NEEDS DE RATING 310.15
RSLV 07/09/2016 07/09/2016 06/06/2017
 
007 (999) OTHER
(FLOOR: 004) MICROWAVE RECEPTACLE NO COVER 314.25
RSLV 07/09/2016 07/09/2016 10/06/2016
 
008 (999) OTHER
(FLOOR: 004) NO 90 DEGREE SWING ON WATER HEATER DS (2) 110.26
RSLV 07/09/2016 07/09/2016 06/06/2017



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order