| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
1 |
(4)#4(1)#8G |
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
1 |
24 CIR 100 AMP |
| D. 3 Phase Over 225 AMPS |
1 |
24 CIR 225 AMP |
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 3) |
APPLICATION FOR CERTIFICATE OF ELECTRICAL INSPECTION NOT ON FILE (FLOOR: 004) MOTORS AND HEATERS NOT FILED FOR |
RSLV |
07/09/2016 |
07/09/2016 |
10/06/2016 |
| |
| 002 |
(999) |
OTHER (FLOOR: 004) NO TIE HANDLES PANEL RP-4S 210.4 |
RSLV |
07/09/2016 |
07/09/2016 |
06/06/2017 |
| |
| 003 |
(999) |
OTHER (FLOOR: 004) NO ARC FLASH STICKERS 110.16 |
RSLV |
07/09/2016 |
07/09/2016 |
10/06/2016 |
| |
| 004 |
(999) |
OTHER (FLOOR: 004) EMT NEEDS SUPPORT ON CEILING 358.30 |
RSLV |
07/09/2016 |
07/09/2016 |
10/06/2016 |
| |
| 005 |
(999) |
OTHER (FLOOR: 004) NO GFI 6 FT OF SINK 210.8 |
RSLV |
07/09/2016 |
07/09/2016 |
10/06/2016 |
| |
| 006 |
(999) |
OTHER (FLOOR: 004) PANEL RP-4S NEEDS DE RATING 310.15 |
RSLV |
07/09/2016 |
07/09/2016 |
06/06/2017 |
| |
| 007 |
(999) |
OTHER (FLOOR: 004) MICROWAVE RECEPTACLE NO COVER 314.25 |
RSLV |
07/09/2016 |
07/09/2016 |
10/06/2016 |
| |
| 008 |
(999) |
OTHER (FLOOR: 004) NO 90 DEGREE SWING ON WATER HEATER DS (2) 110.26 |
RSLV |
07/09/2016 |
07/09/2016 |
06/06/2017 |