BIS Menu  |  Bldg Info Search  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M349195
Premises: 201 WEST 23 STREET MANHATTAN BIN: 1014151     Block: 773   Lot: 40
   
Application Completed and Certified

Filed: 205 W 23 ST Census Tract:   91
SIGN/RADIO SHACK Admin Area:   M - MANHATTAN Inspection Area:   P
NEW YORK, NY 10011 Community Board:   104
DOB Cross Street(s):    7 AVENUE,    8 AVENUE
Status:   C - JOB IS SIGNED OFF 02/18/2014
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   01/13/2014 Job Start Date:   01/27/2014
Last Change:   02/18/2014 Job End Date:   02/15/2014
Appointment Status:   
Last Inspection By:   HUGH MCKESSEY       On     02/15/2014      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010719 Licensee Name: HOWARD ZAMKOFF
Firm: 001943 Firm Name: STAT ELECTRIC INC.
Firm Phone: 718-261-5673  Firm Address: 118-21 QUEENS BLVD.-SUITE 311 FOREST HILLS NY 11375 

Work Started or Filed by Others: NO
Work Category:   U - UN-TAGGED SIGN Work To Be Done:  
6 - GENERAL WIRING
9 - OTHER
Total Fee:  $105.00
Other Work:   SIGN
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   K - Store
Store / Other:   RADIO SHACK
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: 224 SEVENTH AVENUE REALTY
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 1 Tags:

Sign Dimensions : 3 Ft 6 In  BY  7 Ft 4 In  Total Sq. Ft. of Sign: 26
Sign Type : A
Total Circuits: 1 Total Lamps: 0
Watts (Lamps): 0 Number of Trans: 1 VA of Each Trans: 1
Total Watts or VA: 1 A.W. Gauge of Wire: 12 No. of Sockets Per Circuit: 0
Material/Gauge: ALUMINUM PLEXIGLASS LED
Sign Maker : CAPITAL SIGNS
Sign Maker Address: 61 CABOT STREET WEST BABYLON, NY 11704
Shop Address:
Shop Phone:
Shop Location Comments:
Sign Text: RADIO SHACK

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 02/10/2014
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  INSPECTION OF EXISTING ILLUMINATED SIGN TO OBTAIN PERMIT TOLEGALIZE SIGN INSTALLED BY OTHERS TO VERIFY WORK WAS DONE INCOMPLIANCE WITH THE NYC ELECTRICAL CODE SIGN ON WALL

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M349195
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 01/27/2014 02/10/2014 NRS A (35) (4) Y
INSPECTION COMMENTS: ON 7TH AVENUE
 
(2) 02/15/2014 02/18/2014 HMC C R (15) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M349195
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
GROUND: TRANSFORMER ENCLOSURE OUTSIDE BEHIND SIGN NOT BONDED
RSLV 01/27/2014 01/27/2014 02/15/2014
 
002 ( 19) DEFECTIVE WIRING IS IN USE
GROUND: MC CABLE CAME OUT OF STRAIGHT MC CONNECTOR
RSLV 01/27/2014 01/27/2014 02/15/2014
 
003 ( 19) DEFECTIVE WIRING IS IN USE
GROUNND: MC 90* CONNECTOR MISSING SET SCREW
RSLV 01/27/2014 01/27/2014 02/15/2014
 
004 ( 27) ARMORED CABLES INSTALLED WITHOUT INSULATING BUSHINGS
GROUND: CABLE CONNECTED TO TRANSFORMER ENCLOSURE
RSLV 01/27/2014 01/27/2014 02/15/2014



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Bldg Info Search  |  Electrical Inspection Work Order  |  Back