| BUILDING OVERVIEW |
Are Feeders Being Installed? : No |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 19) |
DEFECTIVE WIRING IS IN USE (ALL FLOORS)PANEL 40 A CB FOR OVEN SPLICE W/ #12AWG IN OVEN CABINET (KITCHENAREA) AM 1102A, T 310.16 |
RSLV |
08/22/2014 |
08/22/2014 |
04/12/2016 |
| |
| 002 |
( 16) |
DEFECTIVE LIGHTING FIXTURES ARE IN USE (ALL FLOORS) KITCHEN OPEN WIRING ON LIGHT FIXTURE AM 110.2A |
RSLV |
08/22/2014 |
08/22/2014 |
04/12/2016 |
| |
| 003 |
(109) |
SUFFICIENT WORK SPACE IS NOT PROVIDED/MAINTAINED (ALL FLOORS) KITCHEN NO WORKING SPACE IN FRONT OF PANEL 110.26 |
RSLV |
08/22/2014 |
08/22/2014 |
04/12/2016 |
| |
| 004 |
(211) |
RECEPTACLE IS NOT PROPERLY BONDED/GROUNDED (ALL FLOORS) T-OUT RECEPTICAL NOT PROPERLY GND 250.146 |
RSLV |
08/22/2014 |
08/22/2014 |
04/12/2016 |
| |
| 005 |
(999) |
OTHER (ALL FLOORS) T-OUT RECEPTICAL MORE THAN 1/4" FROM WALL 314.20,21 |
RSLV |
08/22/2014 |
08/22/2014 |
04/12/2016 |
| |
| 006 |
( 34) |
KNOCKOUTS ARE NOT CLOSED IN PANEL BOX (ALL FLOORS) PANEL K/O MISSING |
RSLV |
08/22/2014 |
08/22/2014 |
04/12/2016 |