BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M348189
Premises: 273 BROADWAY MANHATTAN BIN: 1001635     Block: 149   Lot: 33
   
Application Completed and Certified

Filed: 277 BROADWAY Census Tract:   21 Health Area:  7700
CELLER Admin Area:   M - MANHATTAN Inspection Area:   W
NEW YORK, NY 10007 Community Board:   101
DOB Cross Street(s):   CHAMBERS STREET,    READE STREET
Status:   C - JOB IS SIGNED OFF 09/03/2014
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  12/04/2013 7:10 PM
Application Entered:   12/04/2013 Job Start Date:   12/04/2013
Last Change:   09/03/2014 Job End Date:   02/28/2014
Appointment Status:   
Last Inspection By:   ROGALEWSKI, M       On     08/26/2014      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 010069 Licensee Name: PETER AMABILE
Firm: 003346 Firm Name: FLEMINGTON ELEC'L MAINT I
Firm Phone: 646-230-9903  Firm Address: 225 31 STREET BROOKLYN NY 11232 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
Total Fee:  $487.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   O - Office Bldg
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: LESLIE FELDMAN
Owner Business Name: FELDMAN GROUP
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  1  1200
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  2  SET OF 300
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
CEL              100         
Buildings Total              100           
Total Units : 100 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 1
Existing Meters 0 + New Meters 1 - Removed Meters 0 = Total Meters 1

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 12/04/2013 Notice: 1 - FIRST NOTICE 02/26/2014
Power Issued: 12/04/2013 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  FIRE PUMP

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M348189
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 02/12/2014 02/26/2014 DEX A E (30) (2) Y
INSPECTION COMMENTS: CHECK WIRE SIZE HAS TO BE MIN 300 MCM
 
(2) 03/03/2014 03/11/2014 PP1 J R E (20) (0) Y
INSPECTION COMMENTS: (NEED FULL LOAD CALCULATION THEY 250 MCM INSTALLED)
 
(3) 08/26/2014 08/27/2014 MIR C E (30) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M348189
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
BASEMENT: NO NEUTRAL INSTALLED IN FIRE PUMP SERVICE SWITCH. 250.24B
RSLV 02/12/2014 02/12/2014 03/03/2014
 
002 ( 19) DEFECTIVE WIRING IS IN USE
BASEMENT: GROUND NOT CONNECTED IN FIRE ALARM CONTROLLER GROUND
RSLV 02/12/2014 02/12/2014 03/03/2014



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.