BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M348182
Premises: 95 CHAMBERS STREET MANHATTAN BIN: 1001629     Block: 149   Lot: 7501
   
Application Completed and Certified

Filed: 91 CHAMBERS ST Census Tract:   21 Health Area:  7700
CELLAR & 1ST FLOOR Admin Area:   M - MANHATTAN Inspection Area:   W
NEW YORK, NY 10007 Community Board:   101
DOB Cross Street(s):   BROADWAY,    CHURCH STREET
Status:   C - JOB IS SIGNED OFF 07/28/2014
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  12/04/2013 4:44 PM
Application Entered:   12/04/2013 Job Start Date:   12/04/2013
Last Change:   07/28/2014 Job End Date:   03/20/2014
Appointment Status:   
Last Inspection By:   ELLIS DAVID       On     05/27/2014      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 010786 Licensee Name: JOE ZAGO
Firm: 004257 Firm Name: ROMA ELECTRIC CORP
Firm Phone: 718-777-7662  Firm Address: 30-75 14TH STREET ASTORIA NY 11102 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $135.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: PATRICK STEINER
Owner Business Name: 77 READE CONDOMINIUM
Authorized Representative:  MARCO GIOVANNOLI
Relationship To Owner:   GC


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  1  3 #3/0THHN
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  200A
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 1 #10-Wire 0
Existing Meters 35 + New Meters 1 - Removed Meters 1 = Total Meters 35

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 12/04/2013 Notice: 1 - FIRST NOTICE 04/28/2014
Power Issued: 12/04/2013 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  INSTALL NEW RISER & PANEL FOR STORE.

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M348182
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 04/14/2014 04/28/2014 NRS A E (30) (4) Y
INSPECTION COMMENTS: NO SERVICE WORK WAS PERFORMED
 
(2) 05/27/2014 06/04/2014 EID C R E (35) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M348182
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 7) EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT)
BASE: 2" EMT FOR STORE
RSLV 04/14/2014 04/14/2014 05/27/2014
 
002 (132) EQUIPMENT/MATERIAL IS NOT PROPERLY GROUNDED
1FL: E.G.C.NOT TERMINATED IN STORE PANEL
RSLV 04/14/2014 04/14/2014 05/27/2014
 
003 ( 19) DEFECTIVE WIRING IS IN USE
1FL: BLUE LEG NOT TERMINATED IN PANEL
RSLV 04/14/2014 04/14/2014 05/27/2014
 
004 (999) OTHER
BASE: SET SCREWS MISSING FROM 2" COUPLERS. 110.3(B)
RSLV 04/14/2014 04/14/2014 05/27/2014



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back