BIS Menu  |  Electrical Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M347749
Premises: 230 7 AVENUE MANHATTAN BIN: 1014154     Block: 773   Lot: 43
   
Application Completed and Certified

Filed: 230 7 AV Census Tract:   91 Health Area:  5200
2ND, 3RD, 4TH FLOOR Admin Area:   M - MANHATTAN Inspection Area:   P
NEW YORK, NY 10011 Community Board:   104
DOB Cross Street(s):   WEST 23 STREET,    WEST 24 STREET
Status:   C - JOB IS SIGNED OFF 05/12/2014
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  11/20/2013 10:22 AM
Application Entered:   11/20/2013 Job Start Date:   11/20/2013
Last Change:   05/12/2014 Job End Date:   05/31/2014
Appointment Status:   
Last Inspection By:   MOSES, DANIEM       On     05/02/2014      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012072 Licensee Name: CLINTON COURTNEY
Firm: 003770 Firm Name: TRINCITY ELECTRIC, INC
Firm Phone: 718-712-4300  Firm Address: 224-17 MERRICK BLVD SPRINGFIELD GARDENS NY 11413 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $122.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   O - Office Bldg
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: W. BROTHERS REALTY LLC
Owner Business Name: W BROTHERS REALTY LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  3  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
002  2FL  28  20                 
003    28  20                 
004    28  20                 
Buildings Total 84  60    15                  
Total Units : 159 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 04/08/2014
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M347749
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 04/03/2014 04/08/2014 TOR A (55) (4) Y
INSPECTION COMMENTS: NONE
 
(2) 05/02/2014 05/10/2014 DNM C R (20) (0) Y
INSPECTION COMMENTS: C

OBJECTION FOR APPLICATION #: M347749
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
T-OUT: RECEPTACLES SET BACK T-OUT KITCHEN ALL FLOORS. 314.20
RSLV 04/03/2014 04/03/2014 05/02/2014
 
002 (999) OTHER
4 FL: BATH GFCI NOT GROUNDED 250.146
RSLV 04/03/2014 04/03/2014 05/02/2014
 
003 (145) APPLIANCE DISCONNECT NOT PROVIDED/IDENTIFIED.
T-OUT: WATER HEATER HAS NOT DISCONNECT. T-OUT
RSLV 04/03/2014 04/03/2014 05/02/2014
 
004 (999) OTHER
ROOF: EQUIPMENT GROUND FOR COMPRESSOR ON THE ROOF NOT AS PER 250.122
RSLV 04/03/2014 04/03/2014 05/02/2014



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Applications  |  Electrical Inspection Work Order  |  Back