BIS Menu  |  Pre-BIS PA CO Query By Bin  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M347316
Premises: 149 SULLIVAN STREET MANHATTAN BIN: 1008045     Block: 517   Lot: 9
   
Application Completed and Certified

Filed: 149 SULLIVAN ST Census Tract:   49 Health Area:  6800
APT 6B Admin Area:   M - MANHATTAN Inspection Area:   U
NEW YORK, NY 10012 Community Board:   102
DOB Cross Street(s):   PRINCE STREET,    WEST HOUSTON STREET
Status:   C - JOB IS SIGNED OFF 06/23/2014
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  11/07/2013 11:56 PM
Application Entered:   11/07/2013 Job Start Date:   11/08/2013
Last Change:   06/23/2014 Job End Date:   03/31/2014
Appointment Status:   
Last Inspection By:   RACEWICZ, TOMASZ       On     06/09/2014      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012467 Licensee Name: DAMIAN VOUITSIS
Firm: 003735 Firm Name: GALLANT ELEC'L CONST, INC
Firm Phone: 718-318-3733  Firm Address: 260 BEACH 116TH STREET, STE#1 ROCKAWAY PARK NY 11694 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $55.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: CATALINA SANTAMARIA
Authorized Representative:  CATALINA SANTAMARIA
Relationship To Owner:   UNIT OWNER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  1  1-100A 12 CCT.
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
006  6B                   
Buildings Total                     
Total Units : 10 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 04/09/2014
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M347316
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 03/31/2014 04/09/2014 DNM A (40) (5) Y
INSPECTION COMMENTS: NONE
 
(2) 05/15/2014 05/29/2014 DNM J Y (25) (0) Y
INSPECTION COMMENTS: OBJECTION
 
(3) 06/09/2014 06/23/2014 TOR C R (30) (0) Y
INSPECTION COMMENTS: C

OBJECTION FOR APPLICATION #: M347316
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 58) FIXTURE NOT PROPERLY LOCATED IN CLOTHES CLOSET
6B NO AFCI PROTECTION PROVIDED FOR SMOKE DETETOR (210.12B)
RSLV 03/31/2014 03/31/2014 05/15/2014
 
002 (999) OTHER
6B MULTIWIRE BRANCH CIRCUITS OT OF SINGLE TIE OR 2 POLE BREAKER(210.12B)
RSLV 03/31/2014 05/15/2014 06/09/2014
 
003 ( 57) EXPOSED ARMORED CABLES ARE SUBJECT TO PHYSICAL DAMAGE
6B FIXTURE NOT PROPERLY LOCATED IN CLOTLES CLOSET OPEN LUMINARE (410.16)
RSLV 03/31/2014 03/31/2014 05/15/2014
 
004 (999) OTHER
6B MINIMUM (2)(20) AMP SMALL APPLIANCE CIRCUITS REQUIRED FOR KITCHEN COUNTER TOP (210.11C)
RSLV 03/31/2014 05/15/2014 06/09/2014
 
005 (999) OTHER
6B RECEPTACLEA ARE NOT PROPERLY GROUNDED OR BONDED (250.146)
RSLV 03/31/2014 05/15/2014 06/09/2014



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Pre-BIS PA CO Query By Bin  |  Electrical Inspection Work Order  |  Back