| BUILDING OVERVIEW |
Are Feeders Being Installed? : No |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
7 |
ELEVATORS |
| B. Each Additional 10 Floors Or Less |
19 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 33) |
KNOCKOUTS ARE NOT CLOSED IN OUTLET BOX (ALL FLOORS)TOP OF CAR 110.12(A) KO'S ARE NOT CLOSED ( CONTROL BOX) ELEVATOR ID# 1P48960 |
RSLV |
07/13/2019 |
07/13/2019 |
10/17/2019 |
| |
| 002 |
(999) |
OTHER (ALL FLOORS)620.25 GFCI NOT WORK ( INSIDE ELEVATOR CONTROL CAR ) ELEVATOR ID #1P48960-1P47783-1P47787-1P47788 |
RSLV |
07/13/2019 |
07/13/2019 |
10/17/2019 |
| |
| 003 |
(999) |
OTHER (ALL FLOORS)ALL MOTORS AND LIGHTS CAB DISCONNECT SW , NEEDS FULL INSPECTION , NOACCESS ( SEE COMMENTS) ELEVATORS:1P48960-1P47783-1P47784-1P47784-1P47785-1P47786-1P47787-1P47788 |
RSLV |
07/13/2019 |
07/13/2019 |
10/17/2019 |
| |
| 004 |
(999) |
OTHER (ALL FLOORS)620.22 NOT ACCESS FOR OF CAR . ELEVATOR 1P47783 ( FULL INSPECTION) |
RSLV |
07/13/2019 |
07/13/2019 |
10/17/2019 |
| |
| 005 |
(999) |
OTHER (CELLAR)CELLAR 620.24 GFCI DOES NOT WORK PIT ELEVATOR: ID # 1P 48960 |
RSLV |
07/13/2019 |
07/13/2019 |
10/17/2019 |
| |
| 006 |
(999) |
OTHER (CELLAR)CELLAR 620.24 (PIT) LIGHTS AND GFCI NOT WORK. ELEVATOR 1P47786 |
RSLV |
07/13/2019 |
07/13/2019 |
10/17/2019 |
| |
| 007 |
( 33) |
KNOCKOUTS ARE NOT CLOSED IN OUTLET BOX (ROOF) ROOF ( ELEVATOR ROOM) KO'S ARE NOT CLOSED ( TROUGH) |
RSLV |
07/13/2019 |
07/13/2019 |
10/17/2019 |
| |
| 008 |
(999) |
OTHER (ROOF)ROOF ( ELEVATOR ROOM) 620.53 NOT PROVIDED IDENTIFICATION ID ( FROMNYC) , NOT PROVIDED IDENTIFICATION OF THE SUPPLY SIDE OCPD (DISCONNECT LIGHTS CAB) ELEVATOR ID#1P48960 |
RSLV |
07/13/2019 |
07/13/2019 |
10/17/2019 |
| |
| 009 |
(999) |
OTHER (ROOF)ROOF ( ELEVATOR ROOM) 620.53 NOT PROVIDED SIGN TO IDENTIFY THELOCATION OF THE SUPPLY SIDE OCPD ( DISCONNECT LIGHT CAB) ELEVATOR ID# 1P48960-1P47783-1P47784-1P47785-1P47786-1P47786-1P47787-1P47788 |
RSLV |
07/13/2019 |
07/13/2019 |
10/17/2019 |
| |
| 010 |
(999) |
OTHER (ROOF)ROOF ( ELEVATOR ROOM) 620.23 MOTOR DISCONNECT SW NOT PROVIDED IDIDENTIFICATION ( NYC) ELEVATOR 1P47784-1P47783 |
RSLV |
07/13/2019 |
07/13/2019 |
10/17/2019 |
| |
| 011 |
(999) |
OTHER (ROOF) ROOF ( ELEVATOR ROOM) 620.53, 620.55 NOT PROVIDED MOTORDISCONNECTING . ELEVATOR 1P 47787-1P47786 |
RSLV |
07/13/2019 |
07/13/2019 |
10/17/2019 |
| |
| 012 |
(101) |
CONDUCTORS AND/OR EQUIPMENT USED IS NOT APPROVED (ALL FLOORS) MOTORS NOT LISTED T-OUT |
RSLV |
10/17/2019 |
10/17/2019 |
11/12/2019 |