BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M347222
Premises: 242 WEST 14 STREET MANHATTAN BIN: 1080218     Block: 618   Lot: 12
   
Application Completed and Certified

Filed: 242 W 14 ST Census Tract:   77 Health Area:  6100
BASEMENT Admin Area:   M - MANHATTAN Inspection Area:   R
NEW YORK, NY 10011 Community Board:   102
DOB Cross Street(s):    7 AVENUE,    8 AVENUE
Status:   C - JOB IS SIGNED OFF 10/28/2015
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  11/06/2013 4:39 PM
Application Entered:   11/06/2013 Job Start Date:   11/07/2013
Last Change:   10/28/2015 Job End Date:   03/07/2014
Appointment Status:   
Last Inspection By:   MOSES, DANIEM       On     09/28/2015      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 012359 Licensee Name: JOHN S KARALIS
Firm: 003811 Firm Name: TRIBORO ELEC'L CONTR'G CO
Firm Phone: 718-786-0913  Firm Address: 39-02 29TH STREET LONG ISLAND CITY NY 11101 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $367.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Commercial/Residential (1  Stores, 4 Apartments)
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: WILLIAM RADMIN
Owner Business Name: 240-242 LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  5  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  1  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  5  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
002    25  10  20             
004    25  10  20             
Buildings Total   50  20  40                
Total Units : 118 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 5 #4-Wire 1 #10-Wire 0
Existing Meters 6 + New Meters 6 - Removed Meters 6 = Total Meters 6

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 11/06/2013 Notice: 1 - FIRST NOTICE 05/13/2014
Power Issued: 11/06/2013 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  INSTALLING NEW SERVICE EQUIPMENT. COMMERCIAL STORE IS EXISTING, NO WORK TO BE PERFORMED. 1ST AND 3RD FL APTS ARE EXISTING, ONLY PROVIDING NEW PANELS AND RISERS. 2ND AND 4TH FL APTS COMPLETE REWIRE.

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M347222
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 05/07/2014 05/13/2014 DNM V G (75) (5) Y
INSPECTION COMMENTS: NO ACCESS TO APT.1,3. APT.2,4 WAS INSPECTED,SERVICE WAS INSPECTED
 
(2) 09/28/2015 10/01/2015 DNM C R E (40) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M347222
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 11) FEEDER CONDUCTORS ARE NOT OF PROPER SIZE
BSMT: FEEDER CONDUCTORS NOT OF PROPER SIZE.USED #10 BX CABLE FOR80 AMP CIRCUIT BREAKER
RSLV 05/07/2014 05/07/2014 09/28/2015
 
002 ( 53) GFCI HAS NOT BEEN PROVIDED
APT.3,4: G.F.C.I.NOT PROVIDED FOR KITCHEN COUNTER TOP
RSLV 05/07/2014 05/07/2014 09/28/2015
 
003 (999) OTHER
APT.2,4: A/C RECEPTACLES RATED LOWER THAN BRANCH CIRCUITS OVER CUR-RENT PROTECTION DEVICE. 210.21B
RSLV 05/07/2014 05/07/2014 09/28/2015
 
004 (999) OTHER
BSMT: NO FIRE STOP HAS BEEN PROVIDED FOR SERVICE ENTRANCE RACEWAY300.21
RSLV 05/07/2014 05/07/2014 09/28/2015
 
005 ( 53) GFCI HAS NOT BEEN PROVIDED
ROOF: NO G.F.C.I.FOR OUTDOOR RECEPTACLES ON ROOF. 210.8
RSLV 05/07/2014 05/07/2014 09/28/2015



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.