BIS Menu  |  Comments  |  Certs. Occupancy  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M346916
Premises: 225 WEST 24 STREET MANHATTAN BIN: 1014174     Block: 774   Lot: 19
   

DOB NOW: Inspections


Filed: 225 W 24 ST Census Tract:   91 Health Area:  5200
8TH FLOOR Admin Area:   M - MANHATTAN Inspection Area:   P
NEW YORK, NY 10011 Community Board:   104
Special Place Name:   HEALTH CLINIC
DOB Cross Street(s):    7 AVENUE,    8 AVENUE
Status:   K - CLOSED/CANCELLED 04/20/2017
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  10/28/2013 1:53 PM
Application Entered:   10/28/2013 Job Start Date:   11/04/2013
Last Change:   04/20/2017 Job End Date:   12/20/2014
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   JOHN LAUNONEN       On     04/19/2017      
Field Disp:   K - OK TO CANCEL
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010485 Licensee Name: JAMES DIMITRIADIS
Firm: 001636 Firm Name: POSITIVE ELECT'L ASSOC.IN
Firm Phone: 718-482-0202  Firm Address: 40-33 23RD STREET LONG ISLAND CITY NY 11101 

Other Licensees and Firms:
License # Licensee Name Firm # Firm Name Type
010572 FAKATSELIS, CHRISTOS 001636 POSITIVE ELECT'L ASSOC.IN RESPONSIBLE REP

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $432.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   W - School
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: JEAN CLERIE
Owner Business Name: NYCSCA
Authorized Representative:  JAMES DIMITRIADIS
Relationship To Owner:   CONTRACTOR


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  3  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  1  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  3  1-3PH/4W 200 AMP PNL
D. 3 Phase Over 225 AMPS  1  1-3PH/4W 400 AMP PNL
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
008    45  60    25  45  14  20     
Buildings Total 45  60    25  45     20         
Total Units : 198 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: C - CALL TO OFFICE 02/03/2017
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  FASHION INDUSTRIES HS HEALTH CLINIC JOB NO.: 913

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M346916
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 04/20/2015 04/23/2015 DNM N (20) (0) Y
INSPECTION COMMENTS: ELECTRICIAN DID NOT SHOW
 
(2) 04/30/2015 05/06/2015 BUR P (35) (0) Y
INSPECTION COMMENTS: CONTRACTOR DID NOT SET UP AN APPOINTMENT TO GET ACCESS TO CLINIC
 
(3) 08/31/2015 09/02/2015 ECH N (20) (0) Y
INSPECTION COMMENTS: CONTRACTOR NO SHOW AGAIN
 
(4) 09/16/2015 09/22/2015 NRS N (60) (0) Y
INSPECTION COMMENTS: CONTRACTOR NO SHOW
 
(5) 10/06/2015 10/16/2015 EID V (50) (4) Y
INSPECTION COMMENTS: EXAMS ROOMS WERE BEING USED AT TIME OF INSP,NEED TO BE INSPECTED
 
(6) 10/30/2015 11/12/2015 NRS V Y (65) (1) Y
INSPECTION COMMENTS: 343P EXAM ROOM 1 INSPECTED
 
(7) 12/01/2015 12/03/2015 EID N (30) (0) Y
INSPECTION COMMENTS: CONTRACTOR SAID HE CANCELLED APPOINTMENT HE WILL RESCHEDULE FOR ANOTH ER DATE
 
(8) 12/14/2015 12/15/2015 GYM V X (95) (2)
INSPECTION COMMENTS: EXAM ROOMS REQ'D HOSPITAL RECEPTACLES AND CABLES
 
(9) 08/09/2016 08/10/2016 PHG J Y (30) (0)
INSPECTION COMMENTS: F
 
(10) 10/24/2016 10/28/2016 STP V Y (35) (1)
INSPECTION COMMENTS: FAIL. SECOND LEVEL FUSES CHANGED. ADVISORY BOARD DRAWINGS NEEDED, SHOWING BUCKET APPROVED FOR FUTURE USE.
 
(11) 02/03/2017 02/03/2017 CBK H X (60) (0) Y
INSPECTION COMMENTS: OBJECTIONS NOT REMOVED.
 
(12) 04/19/2017 04/20/2017 JUU K R (29) (0)
INSPECTION COMMENTS: ALL WORK FILED UNDER NEW APP. M394088 ,OK TO WITHDRAW

OBJECTION FOR APPLICATION #: M346916
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (255) NO FUSE COORDINATION EXISTS
(ALL FLOORS)BSMT: EL.RM FUSE COORDINATION NEEDED FOR ADDITION OF FUSES AND FEED-ERS(400A LPJ)ON 2ND LVL SWITCH.. AMD 240.12(A)
RSLV 10/06/2015 10/30/2015 04/19/2017
 
002 (999) OTHER
3RD FL: A/C DISC EGC CONDUCTOR NOT SIZED AS PER 250.122
RSLV 10/06/2015 10/06/2015 10/30/2015
 
003 (999) OTHER
2ND FL: SATELLITE PNL NOT ACCURATELY LABELED.. 408.4
RSLV 10/06/2015 10/06/2015 10/30/2015
 
004 (999) OTHER
T-OUT: ARC FLASH WARNING STICKERS NOT INSTALLED ON EQUIP.. 110.16
RSLV 10/06/2015 10/06/2015 10/30/2015
 
005 (999) OTHER
(ALL FLOORS) 3FL: EXAM ROOMS NOT WIRED AS PER 517.13
RSLV 10/30/2015 10/30/2015 10/24/2016
 
006 (139) VERTICAL CONDUCTOR SUPPORT IS NOT PER CODE
(FLOOR: 003) 1 SET. 600KCMIL MISSING SUPPORTED 50FT
RSLV 12/14/2015 12/14/2015 08/09/2016
 
007 (999) OTHER
(FLOOR: 003)EXAM ROOMS HOSPITAL GRADE RECEPTACLES REQ,D ART 517.17.18
RSLV 12/14/2015 12/14/2015 08/09/2016
 
008 ( 4) SERVICE IN EXCESS OF 1000KVA HAS NOT BEEN SUBMITTED FOR APPROVAL
(BASEMENT) NEW RISER AND FUSES 2ND LEVEL FROM BASEMENT.
RSLV 10/24/2016 10/24/2016 04/19/2017



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.