| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
2 |
600 AMP |
| D. 601 Up to 1200 AMPS |
2 |
800 AMP |
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
25 |
#1 AWG |
| C. Over 1/0 to 250 MCM |
3 |
#4/0 AWG |
| D. Over 250 MCM |
6 |
#500 MCM |
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
1 |
100 AMP |
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
27 |
200 AMP |
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 56) |
ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED (ALL FLOORS) GRND: FIRE PUMP CONDUCTORS UNDERSIZED.. AMEND 695.6C |
RSLV |
10/05/2015 |
10/05/2015 |
|
| |
| 002 |
(124) |
TAP CONDUCTORS ARE NOT WITHIN 10 FT OR WITHIN 25 FT AS PER CODE (ALL FLOORS)GRND: TAP CONDUCTORS TO FEED JOCKEY PUMP UNDERSIZED.. 240.21 |
RSLV |
10/05/2015 |
10/05/2015 |
|
| |
| 003 |
(169) |
TEMPORARY CONSTRUCTION WIRING IS NOT REMOVED (ALL FLOORS) GRND: TEMP WIRING NOT REMOVED.. 590.3 |
RSLV |
10/05/2015 |
10/05/2015 |
|
| |
| 004 |
( 26) |
ARMORED CABLES ARE INSTALLED EXPOSED T-OUT: AIR HANDLER OVERFUSED AT 20 AMPS T-OUT.. 110.3 |
OPEN |
10/05/2015 |
10/05/2015 |
|
| |
| 005 |
( 56) |
ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED T-OUT: PANEL USED ZIPPIES FOR GROUNDS.. 250.8 |
OPEN |
10/05/2015 |
10/05/2015 |
|
| |
| 006 |
(340) |
RECEPTACLES NOT TAMPERPROOF T-OUT: RECEPTACLE FOR DISHWASHER NOT TAMPER PROOF.. 406.11 |
OPEN |
10/05/2015 |
10/05/2015 |
|
| |
| 007 |
( 59) |
AFCI PROTECTION HAS NOT BEEN PROVIDED T-OUT: A.F.C.I.PROTECTION NOT PROVIDED.. 210.12 |
OPEN |
10/05/2015 |
10/05/2015 |
|
| |
| 008 |
( 56) |
ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED T-OUT: ZIPPIES USED FOR GROUNDS ON BOXES FOR RECEPTACLES.. 250.8 |
OPEN |
10/05/2015 |
10/05/2015 |
|
| |
| 009 |
(999) |
OTHER T-OUT: NO BUBBLE COVER PROVIDED IN WET LOCATION BALCONY.. 406.8 |
OPEN |
10/05/2015 |
10/05/2015 |
|
| |
| 010 |
(311) |
FIXTURE NOT APPROVED FOR DAMP/WET LOCATION T-OUT: TRIM NEED APPROVAL FOR WET LOCATION.. 110.3 |
OPEN |
10/05/2015 |
10/05/2015 |
|
| |
| 011 |
( 56) |
ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED (ALL FLOORS) GRND: B.L.FNC ON PLASTIC TO FEED MOTORS.. AM 365.10 |
RSLV |
10/05/2015 |
10/05/2015 |
|
| |
| 012 |
( 16) |
DEFECTIVE LIGHTING FIXTURES ARE IN USE ROOF: LIGHT FIXTURE FOR SWIMMING POOL DEFECTIVE.. 110.2A |
OPEN |
10/05/2015 |
10/05/2015 |
|
| |
| 013 |
(999) |
OTHER ROOF: PIPE ON ROOF NOT SUPPORTED.. 344.30 |
OPEN |
10/05/2015 |
10/05/2015 |
|
| |
| 014 |
( 56) |
ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED ROOF: NO P.V.C.PIPE ALLOWED EXCEEDING 3 FLOORS.. 352.10 |
OPEN |
10/05/2015 |
10/05/2015 |
|
| |
| 015 |
( 30) |
OUTLET BOXES ARE NOT SECURED ROOF: 12 X 12 BOX NOT SUPPORTED.. 314.23 |
OPEN |
10/05/2015 |
10/05/2015 |
|
| |
| 016 |
(132) |
EQUIPMENT/MATERIAL IS NOT PROPERLY GROUNDED ROOF: GENERATOR 125 KW NOT PROPERLY GND.. 250.30 |
OPEN |
10/05/2015 |
10/05/2015 |
|
| |
| 017 |
( 22) |
FIXED EQUIPMENT IS NOT PROPERLY GROUNDED ROOF: UNDERSIZE EGND FROM GENERATOR.. 250.122 |
OPEN |
10/05/2015 |
10/05/2015 |
|
| |
| 018 |
(109) |
SUFFICIENT WORK SPACE IS NOT PROVIDED/MAINTAINED ROOF: NO ACCESS TO POOL SPLICE BOX.. 110.26 |
OPEN |
10/05/2015 |
10/05/2015 |
|
| |
| 019 |
( 53) |
GFCI HAS NOT BEEN PROVIDED (ALL FLOORS) GARAGE: GARAGE RECEPTACLE NOT G.F.I. 210.8 |
RSLV |
10/05/2015 |
10/05/2015 |
|
| |
| 020 |
( 24) |
ARMORED CABLES ARE NOT PROPERLY SECURED (ALL FLOORS) GARAGE: F.M.C. CONDUIT NOT PROPERLY SUPPORTED.. 348.30 |
RSLV |
10/05/2015 |
10/05/2015 |
|
| |
| 021 |
(999) |
OTHER GND: EL.RM LOAD OF SERV.CONDUCTORS UNDERSIZE.. 220.40F/P AND PLP.. 230.31GND: F/P ROOM TAP FOR JOCKEY PUMP.. 695.1B(2) |
OPEN |
10/05/2015 |
10/05/2015 |
|