Electrical Application Details for App #: M346821
Premises: 12 VARICK STREET MANHATTAN BIN: 1002169     Block: 190   Lot: 37
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 11 N MOORE ST Census Tract:   33 Health Area:  7700
1-9 FL Admin Area:   M - MANHATTAN Inspection Area:   W
NEW YORK, NY 10013 Community Board:   101
Related Job Number:    121181238
DOB Cross Street(s):   WEST BROADWAY,    VARICK STREET
Status:   C - JOB IS SIGNED OFF 03/11/2016
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  10/24/2013 5:43 PM
Application Entered:   10/24/2013 Job Start Date:   10/24/2013
Last Change:   03/11/2016 Job End Date:   10/23/2014
Appointment Status:   
Last Inspection By:   SOLAVNTO, THOMAS       On     03/11/2016      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  G - NO COMMENT
Objection Disposition:  

License #: 011878 Licensee Name: EDGAR LEVENSTEIN
Firm: 003500 Firm Name: CONTACT PLUS ELEC'L CORP
Firm Phone: 718-254-0291  Firm Address: 2922 SHELL ROAD BROOKLYN NY 11224 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
7 - HVAC WIRING
9 - OTHER
T - TEMPORARY LIGHT & POWER
Total Fee:  $4,249.25
Other Work:   POOL
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: JUSTIN EHRLICH
Owner Business Name: 11 NM VENTURE LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  2  600 AMP
D. 601 Up to 1200 AMPS  2  800 AMP
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  25  #1 AWG
C. Over 1/0 to 250 MCM  3  #4/0 AWG
D. Over 250 MCM  6  #500 MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  1  100 AMP
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  27  200 AMP
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001    80  60    12  80  10         
002    86  120    64  86  18         
003    86  120    64  86  18         
004    86  120    64  86  18         
005    86  120    64  86  18         
006    86  120    64  86  18         
007    100  130    74  100  18         
008    100  130    74  100  18         
009    50  70    34  50  18         
ROF      23  205         
Buildings Total 768  996    516  768     359           
Total Units : 3407 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 19 #10-Wire 1
Existing Meters 0 + New Meters 20 - Removed Meters 0 = Total Meters 20

Power Auth Flag: I - ISSUED Objection Flag: V - OBJECTION(S) EXIST
Power Requested: 10/24/2013 Notice: 1 - FIRST NOTICE 10/15/2015
Power Issued: 10/24/2013 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M346821
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 10/05/2015 10/15/2015 EDB V G (240) (21) Y
INSPECTION COMMENTS: ALL APARTMENTS UNDER COUNTER LIGHTS NOT INSTALLED COULD VERIFY GROUND FOR POOL LIGHT CAN,90% FINISHED
 
(2) ? (0) (0)
INSPECTION COMMENTS: No Inspection Comments For This Application
 
(3) 03/11/2016 03/11/2016 TSO C (25) (0) Y
INSPECTION COMMENTS: UPDATE IN OFFICE.

OBJECTION FOR APPLICATION #: M346821
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
(ALL FLOORS) GRND: FIRE PUMP CONDUCTORS UNDERSIZED.. AMEND 695.6C
RSLV 10/05/2015 10/05/2015
 
002 (124) TAP CONDUCTORS ARE NOT WITHIN 10 FT OR WITHIN 25 FT AS PER CODE
(ALL FLOORS)GRND: TAP CONDUCTORS TO FEED JOCKEY PUMP UNDERSIZED.. 240.21
RSLV 10/05/2015 10/05/2015
 
003 (169) TEMPORARY CONSTRUCTION WIRING IS NOT REMOVED
(ALL FLOORS) GRND: TEMP WIRING NOT REMOVED.. 590.3
RSLV 10/05/2015 10/05/2015
 
004 ( 26) ARMORED CABLES ARE INSTALLED EXPOSED
T-OUT: AIR HANDLER OVERFUSED AT 20 AMPS T-OUT.. 110.3
OPEN 10/05/2015 10/05/2015
 
005 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
T-OUT: PANEL USED ZIPPIES FOR GROUNDS.. 250.8
OPEN 10/05/2015 10/05/2015
 
006 (340) RECEPTACLES NOT TAMPERPROOF
T-OUT: RECEPTACLE FOR DISHWASHER NOT TAMPER PROOF.. 406.11
OPEN 10/05/2015 10/05/2015
 
007 ( 59) AFCI PROTECTION HAS NOT BEEN PROVIDED
T-OUT: A.F.C.I.PROTECTION NOT PROVIDED.. 210.12
OPEN 10/05/2015 10/05/2015
 
008 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
T-OUT: ZIPPIES USED FOR GROUNDS ON BOXES FOR RECEPTACLES.. 250.8
OPEN 10/05/2015 10/05/2015
 
009 (999) OTHER
T-OUT: NO BUBBLE COVER PROVIDED IN WET LOCATION BALCONY.. 406.8
OPEN 10/05/2015 10/05/2015
 
010 (311) FIXTURE NOT APPROVED FOR DAMP/WET LOCATION
T-OUT: TRIM NEED APPROVAL FOR WET LOCATION.. 110.3
OPEN 10/05/2015 10/05/2015
 
011 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
(ALL FLOORS) GRND: B.L.FNC ON PLASTIC TO FEED MOTORS.. AM 365.10
RSLV 10/05/2015 10/05/2015
 
012 ( 16) DEFECTIVE LIGHTING FIXTURES ARE IN USE
ROOF: LIGHT FIXTURE FOR SWIMMING POOL DEFECTIVE.. 110.2A
OPEN 10/05/2015 10/05/2015
 
013 (999) OTHER
ROOF: PIPE ON ROOF NOT SUPPORTED.. 344.30
OPEN 10/05/2015 10/05/2015
 
014 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
ROOF: NO P.V.C.PIPE ALLOWED EXCEEDING 3 FLOORS.. 352.10
OPEN 10/05/2015 10/05/2015
 
015 ( 30) OUTLET BOXES ARE NOT SECURED
ROOF: 12 X 12 BOX NOT SUPPORTED.. 314.23
OPEN 10/05/2015 10/05/2015
 
016 (132) EQUIPMENT/MATERIAL IS NOT PROPERLY GROUNDED
ROOF: GENERATOR 125 KW NOT PROPERLY GND.. 250.30
OPEN 10/05/2015 10/05/2015
 
017 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
ROOF: UNDERSIZE EGND FROM GENERATOR.. 250.122
OPEN 10/05/2015 10/05/2015
 
018 (109) SUFFICIENT WORK SPACE IS NOT PROVIDED/MAINTAINED
ROOF: NO ACCESS TO POOL SPLICE BOX.. 110.26
OPEN 10/05/2015 10/05/2015
 
019 ( 53) GFCI HAS NOT BEEN PROVIDED
(ALL FLOORS) GARAGE: GARAGE RECEPTACLE NOT G.F.I. 210.8
RSLV 10/05/2015 10/05/2015
 
020 ( 24) ARMORED CABLES ARE NOT PROPERLY SECURED
(ALL FLOORS) GARAGE: F.M.C. CONDUIT NOT PROPERLY SUPPORTED.. 348.30
RSLV 10/05/2015 10/05/2015
 
021 (999) OTHER
GND: EL.RM LOAD OF SERV.CONDUCTORS UNDERSIZE.. 220.40F/P AND PLP.. 230.31GND: F/P ROOM TAP FOR JOCKEY PUMP.. 695.1B(2)
OPEN 10/05/2015 10/05/2015