BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M346801
Premises: 72 GREENE STREET MANHATTAN BIN: 1079933     Block: 485   Lot: 8
   
Application Completed and Certified

Filed: 72 GREENE ST Census Tract:   49 Health Area:  6800
BSMT Admin Area:   M - MANHATTAN Inspection Area:   U
NEW YORK, NY 10012 Community Board:   102
Special Place Name:   BSMT SERVICE EQUIPMENT
DOB Cross Street(s):   BROOME STREET,    SPRING STREET
Status:   C - JOB IS SIGNED OFF 02/11/2014
Request Type:   P - PICK-UP eFiled:   YES
Application Entered:   01/16/2014 Job Start Date:   01/17/2014
Last Change:   02/11/2014 Job End Date:   01/20/2014
Appointment Status:    Complaint Number:    1358952
Last Inspection By:   BEST, J       On     01/29/2014      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012379 Licensee Name: ANGELO TZOULIS
Firm: 001965 Firm Name: NEAD ELECTRIC INC.
Firm Phone: 212-764-2752  Firm Address: 530 WEST 50TH STREET NEW YORK NY 10019 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $145.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   O - Office Bldg
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: ABS 72-76 GREENE STREET
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  (4) 500 MCM
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice:  10/24/2013
Power Issued: Response: F - FILED TO REMOVE OBJECTION 01/16/2014

Follow-Up: X - FILED APPL,NOW CLOSED 01/16/2014
Contractor's Comments:  DOUBLE LOGGING & NO GROUNDED SERVICE ENTRANCE. CORRECTIVE WORK PERFORMED TO RECTIFY ITEMS ON VIOLATION #'S 35022066H & 35022067J. WORK ENTAILED REPAIRS TO SERVICE SWITCH

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M346801
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 10/23/2013 10/24/2013 RID W (15) (5)
INSPECTION COMMENTS: SEE VIOLATION DETAILS
 
(2) 01/29/2014 02/11/2014 JSB C R (30) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M346801
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
BSMT SERVICE EQUIPMENTCOM: SERVICE ENTRANCE CONDUCTOR NOT GROUNDED
RSLV 10/23/2013 10/23/2013 01/29/2014
 
002 (999) OTHER
SERVICE EQUIPMENT 400 AMP. 110.14(A)COM: DOUBLE LOGGING LOAD SIDE
RSLV 10/23/2013 10/23/2013 01/29/2014
 
003 ( 29) OUTLET BOXES ARE NOT COVERED
BSMT SERVICE EQUIPMENTCOM: SPLICE BOX NOT COVERED
RSLV 10/23/2013 10/23/2013 01/29/2014
 
004 ( 33) KNOCKOUTS ARE NOT CLOSED IN OUTLET BOX
SERVICE SWITCH 400 AMP,COM: K.O. MISSING
RSLV 10/23/2013 10/23/2013 01/29/2014
 
005 ( 33) KNOCKOUTS ARE NOT CLOSED IN OUTLET BOX
THIS IS NOT A FINAL INSPECTION. SEE THIS COMPLAINT #1358952
RSLV 10/23/2013 10/23/2013 01/29/2014



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.