BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M346598
Premises: 504 CANAL STREET MANHATTAN BIN: 1010333     Block: 595   Lot: 39
   
Application Completed and Certified

Filed: 504 CANAL ST Census Tract:   39 Health Area:  7700
1ST, 2ND AND 3RD FLOORS Admin Area:   M - MANHATTAN Inspection Area:   W
NEW YORK, NY 10013 Community Board:   101
DOB Cross Street(s):   GREENWICH STREET,    WASHINGTON STREET
Status:   C - JOB IS SIGNED OFF 12/29/2014
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  10/21/2013 8:00 AM
Application Entered:   10/21/2013 Job Start Date:   10/21/2013
Last Change:   12/29/2014 Job End Date:   10/20/2014
Appointment Status:   
Last Inspection By:   FENTY, WAYNE       On     12/22/2014      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 010836 Licensee Name: RICHARD SCIOLTO
Firm: 004239 Firm Name: QUEENS ELEC AND SOLAR INC
Firm Phone: 718-472-2145  Firm Address: 23-16 40TH AVENUE LONG ISLAND CITY NY 11101 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
7 - HVAC WIRING
Total Fee:  $171.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Other
Store / Other:   COMMERCIAL
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: VINCENT PONTE
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  1  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001    27  18    12  12     
002    36  26    16             
003    23  30    21             
Buildings Total 86  74    49  24            
Total Units : 245 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 1 #10-Wire 0
Existing Meters 0 + New Meters 1 - Removed Meters 0 = Total Meters 1

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 10/21/2013 Notice: 1 - FIRST NOTICE 10/31/2014
Power Issued: 10/21/2013 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M346598
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 07/11/2014 07/21/2014 NRS Z (0) (0) Y
INSPECTION COMMENTS: NONE
 
(2) 10/28/2014 10/31/2014 EDB A E (60) (8) Y
INSPECTION COMMENTS: NONE
 
(3) 12/22/2014 12/29/2014 WYF C R E (50) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M346598
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (109) SUFFICIENT WORK SPACE IS NOT PROVIDED/MAINTAINED
1FL: NO ACCESS TO GEC CONNECTION. 110.26
RSLV 10/28/2014 10/28/2014 12/22/2014
 
002 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
BSMT: WATER MAIN UNDERSIZE (2 X 4/0 ON #2 AWG) T.25.66
RSLV 10/28/2014 10/28/2014 12/22/2014
 
003 (999) OTHER
CLOSET: RECEPTACLE NOT FLUSH W/WOOD. 314.20,21
RSLV 10/28/2014 10/28/2014 12/22/2014
 
004 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
OUTDOOR: G.F.C.I. NOT W T R. 4006.8A
RSLV 10/28/2014 10/28/2014 12/22/2014
 
005 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
OUTDOOR: A/C UNIT PROPERLY GND (LFMC). 250.112,118
RSLV 10/28/2014 10/28/2014 12/22/2014
 
006 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
KITCHEN: LIGHTS ON SMALL APPLIANCE CKT. 210.52B2
RSLV 10/28/2014 10/28/2014 12/22/2014
 
007 (999) OTHER
KITCHEN: PENINSULA RECEPTACLE MORE THAN 6" OVER HANG. 210.52C5X
RSLV 10/28/2014 10/28/2014 12/22/2014
 
008 ( 63) RECEPTACLE OUTLETS NOT IN SUFFICIENT NUMBER
FRONT: NO RECEPTACLE AT FRONT OF DEWLLING UNIT. 210.52E1
RSLV 10/28/2014 10/28/2014 12/22/2014



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.