| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
1 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
1 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
1 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(109) |
SUFFICIENT WORK SPACE IS NOT PROVIDED/MAINTAINED 1FL: NO ACCESS TO GEC CONNECTION. 110.26 |
RSLV |
10/28/2014 |
10/28/2014 |
12/22/2014 |
| |
| 002 |
( 56) |
ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED BSMT: WATER MAIN UNDERSIZE (2 X 4/0 ON #2 AWG) T.25.66 |
RSLV |
10/28/2014 |
10/28/2014 |
12/22/2014 |
| |
| 003 |
(999) |
OTHER CLOSET: RECEPTACLE NOT FLUSH W/WOOD. 314.20,21 |
RSLV |
10/28/2014 |
10/28/2014 |
12/22/2014 |
| |
| 004 |
( 56) |
ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED OUTDOOR: G.F.C.I. NOT W T R. 4006.8A |
RSLV |
10/28/2014 |
10/28/2014 |
12/22/2014 |
| |
| 005 |
( 22) |
FIXED EQUIPMENT IS NOT PROPERLY GROUNDED OUTDOOR: A/C UNIT PROPERLY GND (LFMC). 250.112,118 |
RSLV |
10/28/2014 |
10/28/2014 |
12/22/2014 |
| |
| 006 |
( 56) |
ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED KITCHEN: LIGHTS ON SMALL APPLIANCE CKT. 210.52B2 |
RSLV |
10/28/2014 |
10/28/2014 |
12/22/2014 |
| |
| 007 |
(999) |
OTHER KITCHEN: PENINSULA RECEPTACLE MORE THAN 6" OVER HANG. 210.52C5X |
RSLV |
10/28/2014 |
10/28/2014 |
12/22/2014 |
| |
| 008 |
( 63) |
RECEPTACLE OUTLETS NOT IN SUFFICIENT NUMBER FRONT: NO RECEPTACLE AT FRONT OF DEWLLING UNIT. 210.52E1 |
RSLV |
10/28/2014 |
10/28/2014 |
12/22/2014 |