BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M346503
Premises: 118 MULBERRY STREET MANHATTAN BIN: 1077169     Block: 205   Lot: 10
   
Application Completed and Certified

Filed: 118 MULBERRY ST Census Tract:   41 Health Area:  6800
BSMT, 1 FL. Admin Area:   M - MANHATTAN Inspection Area:   U
NEW YORK, NY 10013 Community Board:   102
DOB Cross Street(s):   CANAL STREET,    HESTER STREET
Status:   C - JOB IS SIGNED OFF 06/05/2014
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  10/17/2013 7:50 PM
Application Entered:   10/17/2013 Job Start Date:   10/18/2013
Last Change:   06/05/2014 Job End Date:   09/30/2014
Appointment Status:   
Last Inspection By:   AGELONIAS, ANASTASIOS       On     05/21/2014      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 009265 Licensee Name: ARTHUR ROBIN
Firm: 004085 Firm Name: FAITHFUL ELECTRIC INC
Firm Phone: 212-925-6828  Firm Address: 302 GRAND STREET, STORE D NEW YORK NY 10002 

Work Started or Filed by Others: YES
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
7 - HVAC WIRING
Total Fee:  $225.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Commercial/Residential (1  Stores, 13 Apartments)
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: SAO TCHU LUU FAN
Owner Business Name: N/A
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  1  200 AMPS
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  2  3/0
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  200 AMPS
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
GND    20  15    20  10         
Buildings Total 20  15    20     10           
Total Units : 70 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 05/17/2014
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  WORK STARTED BY OTHERS, COMPLETED BY US.

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M346503
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 02/19/2014 03/04/2014 DEX J (75) (0) Y
INSPECTION COMMENTS: NONE
 
(2) 05/05/2014 05/17/2014 LBI A (30) (6) Y
INSPECTION COMMENTS: VIOL
 
(3) 05/21/2014 06/03/2014 IOS C R (30) (0) Y
INSPECTION COMMENTS: REFER TO APP.#M353974

OBJECTION FOR APPLICATION #: M346503
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
CELLAR/#6 GEC,UNDERSIZED FOR 200A SVC/TAB 250.66
RSLV 05/05/2014 05/05/2014 05/21/2014
 
002 (999) OTHER
CELLAR/#6 MBJ UNDERSIZED FOR 200A SVC/250.28D,TAB 250.66
RSLV 05/05/2014 05/05/2014 05/21/2014
 
003 (999) OTHER
CELLAR/SVC TO PANEL 358.30
RSLV 05/05/2014 05/05/2014 05/21/2014
 
004 ( 46) PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY
1FL/ ART 408.4
RSLV 05/05/2014 05/05/2014 05/21/2014
 
005 (999) OTHER
1FL/NO HANDLE TIES 210.4B
RSLV 05/05/2014 05/05/2014 05/21/2014
 
006 (999) OTHER
ROOF/RECEPT IN WET LOCATION NOT WR/4068B
RSLV 05/05/2014 05/05/2014 05/21/2014



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.