BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M346473
Premises: 61 EAST END AVENUE MANHATTAN BIN: 1051382     Block: 1590   Lot: 8
   
Application Completed and Certified

Filed: 75 E END AV Census Tract:   136 Health Area:  3800
11D Admin Area:   M - MANHATTAN Inspection Area:   J
NEW YORK, NY 10028 Community Board:   108
DOB Cross Street(s):   EAST 82 STREET,    EAST 83 STREET
Status:   C - JOB IS SIGNED OFF 04/10/2015
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  10/17/2013 12:28 PM
Application Entered:   10/17/2013 Job Start Date:   10/17/2013
Last Change:   04/10/2015 Job End Date:   10/17/2014
Appointment Status:   
Last Inspection By:   FATA, LUIGI       On     03/23/2015      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010529 Licensee Name: JOHN J MILIOTI
Firm: 004171 Firm Name: HIGH VOLT ELEC CORP. OF
Firm Phone: 347-642-3230  Firm Address: 25-24 82ND STREET AMERICA EAST ELMHURST NY 11370 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $40.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Other
Store / Other:   COOP
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: RAVI NATHAN
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
011  11D                 
Buildings Total                   
Total Units : 13 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: C - CALL TO OFFICE 02/04/2015
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  INSTALL 5 LIGHTS IN CLOSETS THROUGHOUT THE APT. INSTALL 2 GFI OUTLETS IN 2 BATHROOMS WITH INDEPENDENT LINE TO PANEL. PROVIDE A 220 VLT INDEPENDENT LINE FROM PANEL TO KITCHEN FORUSE OF DRYER.

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M346473
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 07/29/2014 08/05/2014 JAP A (50) (5) Y
INSPECTION COMMENTS: NONE
 
(2) 08/18/2014 08/25/2014 TOR N (15) (0) Y
INSPECTION COMMENTS: CALLED CONTRACTOR NO
 
(3) 08/22/2014 08/28/2014 NRS A Y (35) (2) Y
INSPECTION COMMENTS: NONE
 
(4) 12/22/2014 12/29/2014 PHG Z (0) (0) Y
INSPECTION COMMENTS: CANCELD W/OFFICE
 
(5) 01/29/2015 02/04/2015 PDI H X (20) (0) Y
INSPECTION COMMENTS: NO PROGRESS ON JOB
 
(6) 02/20/2015 02/25/2015 LUF Z (0) (0) Y
INSPECTION COMMENTS: CANCELED WITH OFFICE
 
(7) 02/26/2015 03/03/2015 GYM Z (0) (0) Y
INSPECTION COMMENTS: NONE
 
(8) 03/23/2015 03/31/2015 LUF C R (60) (0) Y
INSPECTION COMMENTS: NO COMMENT

OBJECTION FOR APPLICATION #: M346473
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
KITCHEN: RECEPTACLE IN KITCHEN NOT A.F.C.I.PROTECTED. 210.8
RSLV 07/29/2014 01/29/2015 03/23/2015
 
002 (999) OTHER
PANEL: NEUTRAL IS BONDED AFTER SERVICE. 250.24(A)(5)
RSLV 07/29/2014 07/29/2014 08/22/2014
 
003 (999) OTHER
CEILING: OPEN BOXES NO COVERS
RSLV 07/29/2014 01/29/2015 03/23/2015
 
004 (999) OTHER
PANEL: NO PANEL DIRECTORY PROVIDED. 408.4
RSLV 07/29/2014 01/29/2015 03/23/2015
 
005 (999) OTHER
PANEL: OVER CURRENT PROTECTION OVER 6' 7". 404.8,240.24
RSLV 07/29/2014 07/29/2014 08/22/2014
 
006 (341) NORMAL AND EMERGENCY POWER NOT PROVIDED, PATIENT BED LOCATION
11D
RSLV 08/22/2014 01/29/2015 03/23/2015
 
007 (999) OTHER
11D MC BRANCH CIRCUITS GROUNDING NOT AS PER 11.14 AND 250.8
RSLV 08/22/2014 01/29/2015 03/23/2015



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.