BIS Menu  |  Pre-BIS PA CO Query By Bin  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M346089
Premises: 149 SULLIVAN STREET MANHATTAN BIN: 1008045     Block: 517   Lot: 9
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 149 SULLIVAN ST Census Tract:   49 Health Area:  6800
STREET Admin Area:   M - MANHATTAN Inspection Area:   U
NEW YORK, NY 10012 Community Board:   102
Special Place Name:   SIDEWALK
DOB Cross Street(s):   PRINCE STREET,    WEST HOUSTON STREET
Status:   C - JOB IS SIGNED OFF 05/17/2016
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  10/07/2013 12:51 PM
Application Entered:   10/07/2013 Job Start Date:   10/07/2013
Last Change:   05/17/2016 Job End Date:   10/07/2015
Appointment Status:   
Last Inspection By:   URIM SYLA       On     05/05/2016      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011681 Licensee Name: PAUL OLSEN
Firm: 004266 Firm Name: NASH ELECTRIC SERVICES IN
Firm Phone: 646-688-3350  Firm Address: 286 EAST 236TH STREET BRONX NY 10470 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
W - SIDEWALK SHED WIRING & LIGHTING
Total Fee:  $40.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Other
Store / Other:   SHED LIGHTING
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: RACHEL CORNISH
Owner Business Name: G&M EQUIPMENT LEASING
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
SWK                     
Buildings Total                     
Total Units : 4 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: C - CALL TO OFFICE 07/15/2014
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  SIDEWALK SHED LIGHTING FOR G&M EQUIPMENT LEASING ONLY

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M346089
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 04/02/2014 04/10/2014 DNM A (10) (1) Y
INSPECTION COMMENTS: NONE
 
(2) 07/03/2014 07/15/2014 NRS A X (10) (1) Y
INSPECTION COMMENTS: NONE
 
(3) 05/05/2016 05/06/2016 UMS C R (10) (0)
INSPECTION COMMENTS: SHED REMOVED PRIOR TO INSPECTION

OBJECTION FOR APPLICATION #: M346089
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(ALL FLOORS) OUTDOOR: SIDEWALK BRIDGE NOT PROPERLY GROUNDEDCAN BE ENGERIZED. 250.4
RSLV 04/02/2014 07/03/2014 05/05/2016
 
002 ( 33) KNOCKOUTS ARE NOT CLOSED IN OUTLET BOX
(ALL FLOORS) SWS LIGHT OUTLET BOXES
RSLV 07/03/2014 07/03/2014 05/05/2016



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Pre-BIS PA CO Query By Bin  |  Electrical Inspection Work Order  |  Back