| BUILDING OVERVIEW |
Are Feeders Being Installed? : No |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(311) |
FIXTURE NOT APPROVED FOR DAMP/WET LOCATION BATHRM: NOT APPROVED LIGHTS FOR WED/DAMP LOCATION. 410.10 |
OPEN |
11/04/2013 |
11/04/2013 |
|
| |
| 002 |
( 56) |
ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED KITCHEN: PANEL IN COMBUSTIBLE WOOD COVER. 314.20,21 |
OPEN |
11/04/2013 |
11/04/2013 |
|
| |
| 003 |
(128) |
NEUTRAL IS GROUNDED BEYOND LOAD SIDE OF SERVICE SWITCH KITCHEN PANEL: NEUTRAL BONDED AFTER SERV. SW. 250.24A5 |
OPEN |
11/04/2013 |
11/04/2013 |
|
| |
| 004 |
( 25) |
ARMORED CABLES ARE NOT PROPERLY TERMINATED ALL: AC CABLE NOT PROPERLY TERMINATED. 320.40 |
OPEN |
11/04/2013 |
11/04/2013 |
|
| |
| 005 |
(211) |
RECEPTACLE IS NOT PROPERLY BONDED/GROUNDED ALL: RECEPTICAL NOT BONDED/GND. 250.146 |
OPEN |
11/04/2013 |
11/04/2013 |
|
| |
| 006 |
( 59) |
AFCI PROTECTION HAS NOT BEEN PROVIDED PANEL: NO AFCI PROTECTION PROVIDED. 210.12 |
OPEN |
11/04/2013 |
11/04/2013 |
|