BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M345913
Premises: 74 FORSYTH STREET MANHATTAN BIN: 1003951     Block: 306   Lot: 7
   
Application Completed and Certified

Filed: 74 FORSYTH ST Census Tract:   16 Health Area:  7400
FORSYTH ST/ 1-6 Admin Area:   M - MANHATTAN Inspection Area:   V
NEW YORK, NY 10002 Community Board:   103
DOB Cross Street(s):   HESTER STREET,    GRAND STREET
Status:   C - JOB IS SIGNED OFF 12/24/2014
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  10/02/2013 7:04 AM
Application Entered:   10/02/2013 Job Start Date:   10/02/2013
Last Change:   12/24/2014 Job End Date:   09/26/2014
Appointment Status:   
Last Inspection By:   RACEWICZ, TOMASZ       On     12/08/2014      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 012209 Licensee Name: ANTHONY COSCHIGANO III
Firm: 003925 Firm Name: ECNY ELEC'L CONTR'S, INC
Firm Phone: 212-695-9084  Firm Address: 42 WEST 38TH STREET-STE 501 NEW YORK NY 10018 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $805.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Commercial/Residential (2  Stores, 21 Apartments)
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: 145 AVE C,ASSOCIATES,LLC
Authorized Representative:  MINERVA NEGRON
Relationship To Owner:   MANAGER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  600 AMP 3 PHASE
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  24   21 2/3 MC CABLE/ 3- 4/4
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  2  2 SETS 500 MCM AL.
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  3  3- 125 AMP
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 21 #4-Wire 3 #10-Wire 0
Existing Meters 23 + New Meters 24 - Removed Meters 23 = Total Meters 24

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 10/02/2013 Notice: 1 - FIRST NOTICE 09/12/2014
Power Issued: 10/02/2013 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  INSTALLING NEW SERVICE AND APARTMENT FEEDERS

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M345913
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 06/16/2014 06/24/2014 NRS Z (0) (0) Y
INSPECTION COMMENTS: CONTRACTOR CANCELED WITH OFFICE
 
(2) 09/08/2014 09/12/2014 EDB A G (80) (5) Y
INSPECTION COMMENTS: NONE
 
(3) 12/08/2014 12/11/2014 TOR C R E (30) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M345913
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
1FL UNDERSIZE GEC (2X500AL W/1/0 GND) T250.66
RSLV 09/08/2014 09/08/2014 12/08/2014
 
002 (999) OTHER
EL ROOM 1 FL NO FIRE STOP 300.21
RSLV 09/08/2014 09/08/2014 12/08/2014
 
003 ( 16) DEFECTIVE LIGHTING FIXTURES ARE IN USE
EL ROOM OPEN WIRING ON LIGHT FIXTURE AM 110.2A
RSLV 09/08/2014 09/08/2014 12/08/2014
 
004 (999) OTHER
T-OUT NO ARE FLASH WARNING ON NEW EQUIPMENT 110.16
RSLV 09/08/2014 09/08/2014 12/08/2014
 
005 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
1FL BARBER SHOP PANEL: K/O MISSING 110.12A
RSLV 09/08/2014 09/08/2014 12/08/2014



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.