BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M345297
Premises: 501 MADISON AVENUE MANHATTAN BIN: 1035711     Block: 1288   Lot: 21
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 501 MADISON AV Census Tract:   102 Health Area:  4800
E 52ND ST Admin Area:   M - MANHATTAN Inspection Area:   L
NEW YORK, NY 10022 Community Board:   105
Special Place Name:   INNISFREE
DOB Cross Street(s):   EAST 52 STREET,    EAST 53 STREET
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  09/17/2013 3:30 PM
Application Entered:   09/17/2013 Job Start Date:   09/18/2013
Last Change:   08/22/2025 Job End Date:   12/31/2013
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   BINGEL, LORI       On     04/11/2014      
Field Disp:   A - OBJCTN ISSD: JOB COMPLETE
Energize Recommendation:  
Objection Disposition:  

License #: 010905 Licensee Name: SOTIRIOS STATHOPOULOS
Firm: 003195 Firm Name: POLO ELECTRIC CORP. D/B/A
Firm Phone: 212-627-8220  Firm Address: 497 CANAL STREET HELLENIC WIRING CONTRACT NEW YORK NY 10013 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $236.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   O - Office Bldg
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: RICHARD BROOKE
Owner Business Name: 501 MADISON SUTTON LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  1  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
010    68  113    43  173  20  10     
Buildings Total 68  113    43  173        10      
Total Units : 415 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice: 1 - FIRST NOTICE 04/24/2014
Power Issued: Response:  

Follow-Up:
Contractor's Comments:  OFFICE RENOVATION

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M345297
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 04/11/2014 04/24/2014 LBI A (50) (3) Y
INSPECTION COMMENTS: SEE CKTS FOR AC UNIT AND DUCT HEATER IN PANEL AND MECH ROOM. 210..5

OBJECTION FOR APPLICATION #: M345297
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
10FL: EXISTING TAP COND TAPPED AGAIN IN PNL TP-10-1. 240.21B
OPEN 04/11/2014 04/11/2014
 
002 (999) OTHER
10FL: THREE TAP COND IN ONE SPLIT BOLT CONNECTOR. 110.3
OPEN 04/11/2014 04/11/2014
 
003 (315) CONDUCTORS NOT PROPERLY IDENTIFIED
10FL: #2 AND #4 WHITE COND IN EMT IN USE AS UNGROUNDED PHASE. 200.7
OPEN 04/11/2014 04/11/2014



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.