Premises: 231 EAST 87 STREET MANHATTAN BIN: 1048824     Block: 1533   Lot: 122
   
Application Completed and Certified

Filed: 235 E 87 ST Census Tract:   146.02 Health Area:  3700
APT. 9B & 9C Admin Area:   M - MANHATTAN Inspection Area:   J
NEW YORK, NY 10128 Community Board:   108
DOB Cross Street(s):    3 AVENUE,    2 AVENUE
Status:   C - JOB IS SIGNED OFF 03/16/2015
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  08/30/2013 1:59 PM
Application Entered:   08/30/2013 Job Start Date:   09/02/2013
Last Change:   03/16/2015 Job End Date:   09/02/2013
Appointment Status:   
Last Inspection By:   URIM SYLA       On     01/21/2015      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011559 Licensee Name: ALLAN VICTOR
Firm: 003720 Firm Name: RPM ELECTRIC INC
Firm Phone: 212-760-1967  Firm Address: 480 10TH AVENUE NEW YORK NY 10018 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $80.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: JENNIFER CHARMATZ
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  2  12 SPACES
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
009  B/C  16  22  10               
Buildings Total 16  22  10                  
Total Units : 52 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: C - CALL TO OFFICE 12/11/2014
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  COMBINATION OF APT'S # 9B & #9C

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M344652
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 06/09/2014 06/28/2014 PHG V (50) (4) Y
INSPECTION COMMENTS: V
 
(2) 10/28/2014 10/31/2014 UMS V Y (20) (0) Y
INSPECTION COMMENTS: NO ACCESS TO SPLICE BOX FOR MASTER PANEL REST IS INSPECTED
 
(3) 12/04/2014 12/11/2014 PHG V X (60) (1) Y
INSPECTION COMMENTS: COMMON RISER TOP BURRIED IN BOTH APTS-MAIN FUSE IN BSMT 200 AMPS
 
(4) 01/21/2015 01/28/2015 UMS C R (35) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M344652
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 59) AFCI PROTECTION HAS NOT BEEN PROVIDED
9 FL NO AFCI PROVIDED IN LAUDRY CLOSET MASTER BED AND BATH HALL CLOSET 210.12B
RSLV 06/09/2014 06/09/2014 10/28/2014
 
002 ( 19) DEFECTIVE WIRING IS IN USE
9 FL TRANSFORMERS IN CLOSET NOT WIRED RIGHT 110.2
RSLV 06/09/2014 06/09/2014 10/28/2014
 
003 (999) OTHER
9 FL NO ACCESS TO SPLICE BOX FOR MASTER PANNEL 314.29
RSLV 06/09/2014 12/04/2014 01/21/2015
 
004 ( 19) DEFECTIVE WIRING IS IN USE
9FL KITCHEN TRANSFORMERS NOT WIRED CORRECT 110.2LIGHT FIXTURES IN ALL APT PENDING APPROVAL 110.2
RSLV 06/09/2014 06/09/2014 10/28/2014
 
005 (999) OTHER
9FL NO MAIN CRT BREAKER FOR BOTH PANELS WITH COMMON RISER TAP 240.21
RSLV 12/04/2014 12/04/2014 01/21/2015