BIS Menu  |  Bldg Info Search  |  Plumb. Inspections  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M344405
Premises: 80 CHARLES STREET MANHATTAN BIN: 1011207     Block: 620   Lot: 56
   
Application Completed and Certified

Filed: 80 CHARLES ST Census Tract:   73 Health Area:  6400
ROOF Admin Area:   M - MANHATTAN Inspection Area:   R
NEW YORK, NY 10014 Community Board:   102
DOB Cross Street(s):   WEST 4 STREET,    BLEECKER STREET
Status:   C - JOB IS SIGNED OFF 12/02/2013
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  08/23/2013 3:44 PM
Application Entered:   08/23/2013 Job Start Date:   08/23/2013
Last Change:   12/02/2013 Job End Date:   08/24/2013
Appointment Status:   
Last Inspection By:   SCHUSZTER, NORBET       On     11/19/2013      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010785 Licensee Name: VITO MAMMANA
Firm: 002042 Firm Name: MECHANICAL ELECTR'L CORP.
Firm Phone: 718-647-1220  Firm Address: 876 JAMAICA AVENUE BROOKLYN NY 11208 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $40.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   E - Four Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: GARY ABATELLI
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
ROF                       
Buildings Total                       
Total Units : 7 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 10/17/2013
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M344405
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 09/16/2013 09/30/2013 TSO A (30) (4) Y
INSPECTION COMMENTS: *PANEL LOCATED INSIDE SHAFT NO FLOOR *DANGEROUS* **SEE OBJECTIONS
 
(2) 10/11/2013 10/17/2013 IOS A Y (35) (2) Y
INSPECTION COMMENTS: NONE
 
(3) 11/19/2013 12/02/2013 NRS C R (10) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M344405
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
ROOF: LFMC > 6' ALL THROUGH-OUT DECK...... - 350.12 AMEND
RSLV 09/16/2013 09/16/2013 10/11/2013
 
002 (999) OTHER
ROOF: PANEL LOCATED IN SHAFT - NO WORKING SPACE..... - 110.3
RSLV 09/16/2013 10/11/2013 11/19/2013
 
003 (999) OTHER
ROOF: RECEPTACLE COVERS NOT FOR OUTDOOR USE....... - 406.8
RSLV 09/16/2013 09/16/2013 10/11/2013
 
004 (999) OTHER
ROOF: G.F.C.I.NOT W/R TYPE...... - 406.8
RSLV 09/16/2013 09/16/2013 10/11/2013
 
005 (999) OTHER
ROOF: ALUMINUM CONDUIT UNDER DESK NOT SUPPORTED. 344.30
RSLV 10/11/2013 10/11/2013 11/19/2013
 
006 (999) OTHER
ROOF: RECEPTACLE UNDER SINK NOT G.F.C.I./W/R TYPE. 210.8
RSLV 10/11/2013 10/11/2013 11/19/2013



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Bldg Info Search  |  Plumb. Inspections  |  Electrical Inspection Work Order  |  Back