| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
33 |
#6-3 AC |
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
33 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
INSP ID |
FIELD DATE |
DISP DATE |
INSP ID |
FLD DISP |
OBJ DISP |
ENRG REC |
TIME INSP |
REINSP DATE |
NEW OBJ |
APPT FLAG |
| |
| (1) |
03/23/2015 |
03/31/2015 |
LUF |
V |
|
|
(60) |
|
(7) |
Y |
| INSPECTION COMMENTS:
|
NO ACCESS TO THE FOLLOWING APARTMENTS 6-C,6-E,5-A THRU -D,6-D,6-F, 4A,B,C,D,F,3-A,B,E,F,1-B,C,2-A,B,E
|
| |
| (2) |
05/27/2015 |
06/02/2015 |
GYM |
A |
Y |
|
(75) |
|
(4) |
Y |
| INSPECTION COMMENTS:
|
INSPETD APTS. 60 6A 6F 5F 4B 2C 1B ONLY
|
| |
| (3) |
11/19/2015 |
11/25/2015 |
UMS |
A |
R |
E |
(120) |
|
(4) |
Y |
| INSPECTION COMMENTS:
|
NO ACCESS TO 3RD FLOOR APARTMENTS. REST OF FLOORS HAVE BEEN INSPECTED
|
| |
| (4) |
12/23/2015 |
12/24/2015 |
LUF |
C |
R |
|
(30) |
|
(0) |
|
| INSPECTION COMMENTS:
|
NONE
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 34) |
KNOCKOUTS ARE NOT CLOSED IN PANEL BOX BASEMENT: KNOCKOUTS MISSING IN MAIN METER BANK.. 110.12(A) |
RSLV |
03/23/2015 |
03/23/2015 |
05/27/2015 |
| |
| 002 |
( 22) |
FIXED EQUIPMENT IS NOT PROPERLY GROUNDED 6B: CABLES NOT SECURED IN PANEL.. 320.30 |
RSLV |
03/23/2015 |
05/27/2015 |
11/19/2015 |
| |
| 003 |
(999) |
OTHER 6B: TAMPER RESISTANT RECEPTACLES MISSING THROUGH-OUT APT.. 406.11 |
RSLV |
03/23/2015 |
05/27/2015 |
11/19/2015 |
| |
| 004 |
( 46) |
PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY 6B: PANEL SCHEDULE MISSING.. 408.4 |
RSLV |
03/23/2015 |
05/27/2015 |
11/19/2015 |
| |
| 005 |
( 46) |
PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY 6A: PANEL SCHEDULE MISSING.. 408.4 |
RSLV |
03/23/2015 |
05/27/2015 |
11/19/2015 |
| |
| 006 |
(999) |
OTHER 3D: TAMPER RESISTANT RECEPT MISSING THROUGH-OUT APT.. 408.46.11 |
RSLV |
03/23/2015 |
05/27/2015 |
11/19/2015 |
| |
| 007 |
( 46) |
PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY 1A) PANEL SCHEDULE MISSING.. 408.4 |
RSLV |
03/23/2015 |
05/27/2015 |
11/19/2015 |
| |
| 008 |
(999) |
OTHER ALL FLOORS OUTLET BOXES ARE NOT GROUNDED AR. 250.146 |
RSLV |
05/27/2015 |
05/27/2015 |
11/19/2015 |
| |
| 009 |
( 59) |
AFCI PROTECTION HAS NOT BEEN PROVIDED 1ST FLOOR APT. 1B |
RSLV |
05/27/2015 |
05/27/2015 |
11/19/2015 |
| |
| 010 |
(999) |
OTHER 1ST FLOOR NO TAMPER RESISTANT RECEPTS PROVIDED ART 406.11(APT 1BB) |
RSLV |
05/27/2015 |
05/27/2015 |
11/19/2015 |
| |
| 011 |
(999) |
OTHER 1ST FLOOR DOUBLE LUGING BREAKERS APT 1B ART. 110.14 |
RSLV |
05/27/2015 |
05/27/2015 |
11/19/2015 |
| |
| 012 |
(999) |
OTHER (ALL FLOORS)APT 2F MULTIPLE UNGROUNDED CONDUCTORS IN ONE BREAKER IN PANEL. 110.14A |
RSLV |
11/19/2015 |
11/19/2015 |
12/23/2015 |
| |
| 013 |
(999) |
OTHER (ALL FLOORS) APT 4E , THROUGONUT RECEPTACLES NOT OF TR TYPE 406.11 |
RSLV |
11/19/2015 |
11/19/2015 |
12/23/2015 |
| |
| 014 |
(999) |
OTHER (ALL FLOORS) APT 4E RECEPTACLES NOT GROUNDED 250.146 |
RSLV |
11/19/2015 |
11/19/2015 |
12/23/2015 |
| |
| 015 |
(999) |
OTHER (ALL FLOORS) ALL NO DIRECTORY PROVIDED FOR PANELS 408.4 |
RSLV |
11/19/2015 |
11/19/2015 |
12/23/2015 |