BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M342958
Premises: 125 EAST 72 STREET MANHATTAN BIN: 1042844     Block: 1407   Lot: 16
   
Application Completed and Certified

Filed: 125 E 72 ST Census Tract:   128 Health Area:  4100
1 Admin Area:   M - MANHATTAN Inspection Area:   K
NEW YORK, NY 10021 Community Board:   108
Special Place Name:   MANHATTAN PEDIATRICS
DOB Cross Street(s):   PARK AVENUE,    LEXINGTON AVENUE
Status:   C - JOB IS SIGNED OFF 11/07/2013
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  07/17/2013 5:39 PM
Application Entered:   07/17/2013 Job Start Date:   07/18/2013
Last Change:   11/07/2013 Job End Date:   07/21/2013
Appointment Status:   
Last Inspection By:   MOSES, DANIEM       On     08/23/2013      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011919 Licensee Name: JOSEPH E FORAN
Firm: 003982 Firm Name: PM ELEC'L MAINTENANCE INC
Firm Phone: 212-481-9526  Firm Address: 15 EAST 40TH ST, SUITE 303 NEW YORK NY 10016 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $270.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   I - Hospital Or Health Facility
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: GARY EDELSTEIN
Owner Business Name: EDELSTEIN RATNER
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  2  2-SETS 3/0
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  2  2- 225AMP
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001    36  45    26  36  22     
Buildings Total 36  45    26  36     22         
Total Units : 173 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 08/05/2013
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  RENOVATION OF EXISTING SPACE

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M342958
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 07/30/2013 08/05/2013 JKF A (60) (4) Y
INSPECTION COMMENTS: NONE
 
(2) 08/23/2013 09/03/2013 DNM C R (30) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M342958
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
PANEL: HANDLE TIES. 210.4
RSLV 07/30/2013 07/30/2013 08/23/2013
 
002 (999) OTHER
PANEL: GROUPING CIRCUIT. 210.4
RSLV 07/30/2013 07/30/2013 08/23/2013
 
003 ( 53) GFCI HAS NOT BEEN PROVIDED
REAR: YARD AT A/C CONDENSER
RSLV 07/30/2013 07/30/2013 08/23/2013
 
004 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
YARD A/C CONDENSER GROUND TO BE #10 AWG
RSLV 07/30/2013 07/30/2013 08/23/2013



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.