BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M342653
Premises: 323 EAST 78 STREET MANHATTAN BIN: 1045244     Block: 1453   Lot: 14
   
Application Completed and Certified

Filed: 323 E 78 ST Census Tract:   134 Health Area:  4200
4/FL AND 5/FL Admin Area:   M - MANHATTAN Inspection Area:   K
NEW YORK, NY 10075 Community Board:   108
Related Job Number:    120186164
DOB Cross Street(s):    2 AVENUE,    1 AVENUE
Status:   C - JOB IS SIGNED OFF 10/04/2014
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  07/10/2013 10:39 PM
Application Entered:   07/10/2013 Job Start Date:   07/11/2013
Last Change:   10/04/2014 Job End Date:   12/13/2013
Appointment Status:   
Last Inspection By:   URIM SYLA       On     08/11/2014      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 012361 Licensee Name: ANGELO DOMINGUEZ
Firm: 004263 Firm Name: ALLTECH ELECL CONTNG CORP
Firm Phone: 646-491-2088  Firm Address: 227 SEA BREEZE AVE., STE 201 BROOKLYN NY 11224 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $203.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: TERRENCE LOWENBERG
Owner Business Name: ICON REALTY MANAGEMENT
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  2  100 S/S
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  2  2 SET OF #3 WIRE
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  2  100 AMP PANEL
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
004    50  55  20  50             
005    50  53  20  50             
Buildings Total 100  108  12  40  100                
Total Units : 360 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 2 #10-Wire 0
Existing Meters 9 + New Meters 2 - Removed Meters 2 = Total Meters 9

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 07/10/2013 Notice: 1 - FIRST NOTICE 07/16/2014
Power Issued: 07/10/2013 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M342653
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 07/07/2014 07/16/2014 UMS A G (50) (5) Y
INSPECTION COMMENTS: INSPECT 4B APARTMENT ONLY
 
(2) 08/11/2014 08/14/2014 UMS C R E (40) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M342653
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
BASEMENT: SERVICE SWITCHES MISSING KO SEALS. 110.12A
RSLV 07/07/2014 07/07/2014 08/11/2014
 
002 (999) OTHER
5TH FL.PANEL: BRANCH CIRCUIT CONDUCTORS USED TO WIRE A/C UNITS NOTGROUNDED PROPERLY AT THE PANEL. 250.35
RSLV 07/07/2014 07/07/2014 08/11/2014
 
003 (999) OTHER
ROOF: 12 AWG USED TO WIRE LOAD SIDE OF A/C DISCONNECT WHICH IS OVER-FUSD. 240.4D5
RSLV 07/07/2014 07/07/2014 08/11/2014
 
004 (999) OTHER
ROOF: LFMC USED TO WIRE A/C UNITS NOT SUPPORTED PROPERLY. 350.30
RSLV 07/07/2014 07/07/2014 08/11/2014
 
005 (999) OTHER
BASEMENT: SERVICE DISCONNECT SWITCH NOT GROUPED IN ONE LOCATION WITHOTHER SERVICE DISCONNECTS. 230.72A
RSLV 07/07/2014 07/07/2014 08/11/2014



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.