BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M342647
Premises: 5 GREAT JONES STREET MANHATTAN BIN: 1008473     Block: 530   Lot: 10
   
Application Completed and Certified

Filed: 5 GREAT JONES ST Census Tract:   55.02 Health Area:  5700
APT 3 Admin Area:   M - MANHATTAN Inspection Area:   S
NEW YORK, NY 10012 Community Board:   102
DOB Cross Street(s):   GREAT JONES ALLEY,    LAFAYETTE STREET
Status:   C - JOB IS SIGNED OFF 04/23/2014
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  07/10/2013 7:30 PM
Application Entered:   07/10/2013 Job Start Date:   07/10/2013
Last Change:   04/23/2014 Job End Date:   12/22/2014
Appointment Status:   
Last Inspection By:   RACEWICZ, TOMASZ       On     01/13/2014      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 011853 Licensee Name: APPOLINAIRE LAUTURE
Firm: 003458 Firm Name: APPO ELECTRICAL, LLC
Firm Phone: 718-726-0814  Firm Address: 36-32 34TH STREET, FLR3 LONG ISLAND CITY NY 11106 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $118.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Commercial/Residential (1  Stores, 4 Apartments)
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: PAUL OLIVER
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
003    26  35    21    40         
Buildings Total 26  35    21       40           
Total Units : 122 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 1 #10-Wire 0
Existing Meters 1 + New Meters 1 - Removed Meters 1 = Total Meters 1

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 07/10/2013 Notice: 1 - FIRST NOTICE 01/07/2014
Power Issued: 07/10/2013 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M342647
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 12/26/2013 01/07/2014 NRS A E (70) (10) Y
INSPECTION COMMENTS: NONE
 
(2) 01/13/2014 01/21/2014 TOR C R E (35) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M342647
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
#3: OUTLET BOXES SET TOO DEEP IN BASEBAORDS & CABINETS. 314.20
RSLV 12/26/2013 12/26/2013 01/13/2014
 
002 ( 59) AFCI PROTECTION HAS NOT BEEN PROVIDED
#3
RSLV 12/26/2013 12/26/2013 01/13/2014
 
003 ( 16) DEFECTIVE LIGHTING FIXTURES ARE IN USE
#3: IN ALL BATHROOM CEILINGS,KIDS HALL & CLOSET LIGHTS
RSLV 12/26/2013 12/26/2013 01/13/2014
 
004 (211) RECEPTACLE IS NOT PROPERLY BONDED/GROUNDED
#3: THROUGH-OUT
RSLV 12/26/2013 12/26/2013 01/13/2014
 
005 (132) EQUIPMENT/MATERIAL IS NOT PROPERLY GROUNDED
#3: MORE THAN 6'FMC USED FOR FEEDING APARTMENT PANEL
RSLV 12/26/2013 12/26/2013 01/13/2014
 
006 (999) OTHER
#3: STUDY HAS NO LIGHT OR SWITCHED OUTLET. 210.70
RSLV 12/26/2013 12/26/2013 01/13/2014
 
007 (229) SPLICE BOXES NOT ACCESSIBLE
#3: NO ACCESS TO UNDER CABINET LED LIGHT DRIVER
RSLV 12/26/2013 12/26/2013 01/13/2014
 
008 (999) OTHER
#3: OPEN CEILING BOXES IN HALL CLOSETS. 314.25
RSLV 12/26/2013 12/26/2013 01/13/2014
 
009 ( 19) DEFECTIVE WIRING IS IN USE
#3: A/C ROOF DISCONNECTS BONDED AT CENTER OF CONCENTRIC KO
RSLV 12/26/2013 12/26/2013 01/13/2014
 
010 (999) OTHER
#3: A/CS (2) OVER FUSED. 440.22(C)
RSLV 12/26/2013 12/26/2013 01/13/2014



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order