| BUILDING OVERVIEW |
Are Feeders Being Installed? : No |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
1 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(999) |
OTHER #3: OUTLET BOXES SET TOO DEEP IN BASEBAORDS & CABINETS. 314.20 |
RSLV |
12/26/2013 |
12/26/2013 |
01/13/2014 |
| |
| 002 |
( 59) |
AFCI PROTECTION HAS NOT BEEN PROVIDED #3 |
RSLV |
12/26/2013 |
12/26/2013 |
01/13/2014 |
| |
| 003 |
( 16) |
DEFECTIVE LIGHTING FIXTURES ARE IN USE #3: IN ALL BATHROOM CEILINGS,KIDS HALL & CLOSET LIGHTS |
RSLV |
12/26/2013 |
12/26/2013 |
01/13/2014 |
| |
| 004 |
(211) |
RECEPTACLE IS NOT PROPERLY BONDED/GROUNDED #3: THROUGH-OUT |
RSLV |
12/26/2013 |
12/26/2013 |
01/13/2014 |
| |
| 005 |
(132) |
EQUIPMENT/MATERIAL IS NOT PROPERLY GROUNDED #3: MORE THAN 6'FMC USED FOR FEEDING APARTMENT PANEL |
RSLV |
12/26/2013 |
12/26/2013 |
01/13/2014 |
| |
| 006 |
(999) |
OTHER #3: STUDY HAS NO LIGHT OR SWITCHED OUTLET. 210.70 |
RSLV |
12/26/2013 |
12/26/2013 |
01/13/2014 |
| |
| 007 |
(229) |
SPLICE BOXES NOT ACCESSIBLE #3: NO ACCESS TO UNDER CABINET LED LIGHT DRIVER |
RSLV |
12/26/2013 |
12/26/2013 |
01/13/2014 |
| |
| 008 |
(999) |
OTHER #3: OPEN CEILING BOXES IN HALL CLOSETS. 314.25 |
RSLV |
12/26/2013 |
12/26/2013 |
01/13/2014 |
| |
| 009 |
( 19) |
DEFECTIVE WIRING IS IN USE #3: A/C ROOF DISCONNECTS BONDED AT CENTER OF CONCENTRIC KO |
RSLV |
12/26/2013 |
12/26/2013 |
01/13/2014 |
| |
| 010 |
(999) |
OTHER #3: A/CS (2) OVER FUSED. 440.22(C) |
RSLV |
12/26/2013 |
12/26/2013 |
01/13/2014 |