BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M342578
Premises: 415 EAST 75 STREET MANHATTAN BIN: 1045923     Block: 1470   Lot: 10
   
Application Completed and Certified

Filed: 415 E 75 ST Census Tract:   132 Health Area:  4300
BASEMENT Admin Area:   M - MANHATTAN Inspection Area:   K
NEW YORK, NY 10021 Community Board:   108
DOB Cross Street(s):    1 AVENUE,    YORK AVENUE
Status:   C - JOB IS SIGNED OFF 12/05/2014
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  07/09/2013 12:27 PM
Application Entered:   07/09/2013 Job Start Date:   07/10/2013
Last Change:   12/05/2014 Job End Date:   07/09/2014
Appointment Status:   
Last Inspection By:   MOSES, DANIEM       On     11/06/2014      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 011171 Licensee Name: TREVOR DUNWELL
Firm: 002607 Firm Name: APPROVED ELECTRIC CORP.
Firm Phone: 718-882-3145  Firm Address: 3550 WHITE PLAINS ROAD STE #9 BRONX NY 10467 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
Total Fee:  $340.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: ANNIE ASSOULINE
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  2  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  2  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  1  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 20 #4-Wire 0 #10-Wire 0
Existing Meters 20 + New Meters 20 - Removed Meters 20 = Total Meters 20

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 07/09/2013 Notice: 1 - FIRST NOTICE 06/17/2014
Power Issued: 07/09/2013 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M342578
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 06/05/2014 06/17/2014 PHG A E (50) (7) Y
INSPECTION COMMENTS: NONE
 
(2) 11/06/2014 12/05/2014 DNM C R E (30) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M342578
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
BASEMENT TAP FOR OFFICE OVER 25 FEET 240.21
RSLV 06/05/2014 06/05/2014 11/06/2014
 
002 (999) OTHER
BASEMENT NO HANDLE TIES PROVIDED FOR MULTIWIRE CKT 210.4
RSLV 06/05/2014 06/05/2014 11/06/2014
 
003 ( 46) PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY
BASEMENT NO DIRECTORY FOR PLP PANEL 408.4
RSLV 06/05/2014 06/05/2014 11/06/2014
 
004 (999) OTHER
BASEMENT 2 WIRES UNDER 1 BREAKER IN PLP PANEL 110.2
RSLV 06/05/2014 06/05/2014 11/06/2014
 
005 (315) CONDUCTORS NOT PROPERLY IDENTIFIED
BASEMENT WIRE TAPEP ROD IN PLP PANEL 200.6
RSLV 06/05/2014 06/05/2014 11/06/2014
 
006 (999) OTHER
BASEMENT BOX FLL IN BATHROOM TOO MANY WIRES 314.16B
RSLV 06/05/2014 06/05/2014 11/06/2014
 
007 (999) OTHER
BASEMENT IMPROPER TAP OF NEUTRAL WIRE IN HALL BOXES VRANCH CKTS ART-100
RSLV 06/05/2014 06/05/2014 11/06/2014



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.