Electrical Application Details for App #: M342289
Premises: 49 EAST 34 STREET MANHATTAN BIN: 1017101     Block: 864   Lot: 28
   
Application Completed and Certified

Filed: 47 E 34 ST Census Tract:   74 Health Area:  5200
GROUND FLOOR Admin Area:   M - MANHATTAN Inspection Area:   P
NEW YORK, NY 10016 Community Board:   106
Special Place Name:   KNOCKOUT RENOVATION
DOB Cross Street(s):   MADISON AVENUE,    PARK AVENUE
Status:   C - JOB IS SIGNED OFF 08/12/2015
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  06/30/2013 1:02 PM
Application Entered:   06/30/2013 Job Start Date:   07/01/2013
Last Change:   08/12/2015 Job End Date:   11/15/2013
Appointment Status:   
Last Inspection By:   RACEWICZ, TOMASZ       On     07/21/2015      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010224 Licensee Name: PAUL VERARDI
Firm: 002161 Firm Name: PAUL VERARDI
Firm Phone: 718-436-1650  Firm Address: 449 39TH STREET BROOKLYN NY 11232 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
7 - HVAC WIRING
8 - BOILER/BURNER WIRING
Total Fee:  $194.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   K - Store
Store / Other:   KITCHEN SHOWROOM
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: KEITH STEIER
Owner Business Name: KNOCKOUT RENOVATION
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  4- #6'S
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  24 CIRCUIT
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS    16  30    12  16         
GND    100  50    40  100         
Buildings Total 116  80    52  116              
Total Units : 369 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 12/06/2013
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M342289
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 11/25/2013 12/06/2013 EDB A (60) (10) Y
INSPECTION COMMENTS: NONE
 
(2) 05/11/2015 05/14/2015 ECH J Y (45) (0) Y
INSPECTION COMMENTS: WORK NOT COMPLETED
 
(3) 07/21/2015 07/27/2015 TOR C R (30) (0) Y
INSPECTION COMMENTS: RESOLVED ALL OBJECTIONS

OBJECTION FOR APPLICATION #: M342289
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
PANELS MULTIWIRE CKT: NO GROUPED, NO SIMULTI. TRIP. 210.4
RSLV 11/25/2013 05/11/2015 07/21/2015
 
002 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
GND: 30A OVEN UNDER SIZE E.G.C. 250.122
RSLV 11/25/2013 11/25/2013 05/11/2015
 
003 ( 36) CONDUCTORS ARE NOT PROPERLY COLOR CODED
BSMT PANEL: COLOR CODE ON POWER. 210.5
RSLV 11/25/2013 11/25/2013 05/11/2015
 
004 ( 21) CONDUCTORS HAVE NOT BEEN PROPERLY DE-RATED
BSMT: PANEL: 10 CURREND CONDUCTOR IN RACEWAY. 310.15B2A
RSLV 11/25/2013 05/11/2015 07/21/2015
 
005 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
BSMT: NO E. G. C. IN F M C. 250.112
RSLV 11/25/2013 05/11/2015 07/21/2015
 
006 ( 29) OUTLET BOXES ARE NOT COVERED
BSMT: NO OUTLET COVERS. 314.25
RSLV 11/25/2013 05/11/2015 07/21/2015
 
007 ( 46) PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY
ROOF: NO PANEL DIRECTORY. 408.4
RSLV 11/25/2013 11/25/2013 05/11/2015
 
008 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
ROOF: GFCI NOT WEATHER-RESISTANT TYPE. 406.8A,B
RSLV 11/25/2013 11/25/2013 05/11/2015
 
009 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
ROOF: A/C CONDENSER: NO E.G.C (60A 3 PHASE). 250.112
RSLV 11/25/2013 11/25/2013 05/11/2015
 
010 ( 16) DEFECTIVE LIGHTING FIXTURES ARE IN USE
GND BOILER RM: DEFECTIVE LIGHT FIXTURE. AM 110.2A
RSLV 11/25/2013 11/25/2013 05/11/2015