BIS Menu  |  Property Permits  |  DOB Violations  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M342137
Premises: 8 EAST 85 STREET MANHATTAN BIN: 1046825     Block: 1496   Lot: 65
   
Application Completed and Certified

Filed: 10 E 85 ST Census Tract:   150.01 Health Area:  3600
6D Admin Area:   M - MANHATTAN Inspection Area:   J
NEW YORK, NY 10028 Community Board:   108
DOB Cross Street(s):    5 AVENUE,    MADISON AVENUE
Status:   C - JOB IS SIGNED OFF 03/29/2014
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  06/26/2013 3:56 PM
Application Entered:   06/26/2013 Job Start Date:   06/27/2013
Last Change:   03/29/2014 Job End Date:   12/31/2014
Appointment Status:   
Last Inspection By:   GANITIS, PHILLIP       On     03/21/2014      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 010587 Licensee Name: HARRY FRENKEL
Firm: 002697 Firm Name: APOLLO ELECTRIC INC.
Firm Phone: 212-627-2561  Firm Address: 127 WEST 24TH ST,5TH FL STE#A NEW YORK NY 10011 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
T - TEMPORARY LIGHT & POWER
Total Fee:  $146.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: MICHAEL SETZEN
Owner Business Name: PROPERTY OWNER
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  1  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
006  6D  43    29  65         
Buildings Total 43    29  65              
Total Units : 145 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 1 #10-Wire 0
Existing Meters 1 + New Meters 1 - Removed Meters 1 = Total Meters 1

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 06/26/2013 Notice: 1 - FIRST NOTICE 03/12/2014
Power Issued: 06/26/2013 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M342137
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 02/27/2014 03/12/2014 IOS A E (65) (3) Y
INSPECTION COMMENTS: NONE
 
(2) 03/21/2014 03/29/2014 PHG C R E (20) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M342137
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
APT 60 A/C RECEPTACLES AND CLOCK OUTLETS ARE NOT (TR) 406.11
RSLV 02/27/2014 02/27/2014 03/21/2014
 
002 (999) OTHER
APT 60 GEM BOXES ARE NOT BONDED FOR A/C BOX OUT 250.146
RSLV 02/27/2014 02/27/2014 03/21/2014
 
003 (999) OTHER
BSMT ELECTRICAL PENETRATIONS ARE NOT FIRESTOPPED 300.21
RSLV 02/27/2014 02/27/2014 03/21/2014