BIS Menu  |  Applications  |  After Hours Variance Permits  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M341458
Premises: 400 EAST 74 STREET MANHATTAN BIN: 1045887     Block: 1468   Lot: 45
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 400 E 74 ST Census Tract:   124
2,3,14,22,24, & 25 Admin Area:   M - MANHATTAN Inspection Area:   K
NEW YORK, NY 10021 Community Board:   108
Special Place Name:   1ST AVE
DOB Cross Street(s):    1 AVENUE,    YORK AVENUE
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   06/10/2013 Job Start Date:   05/28/2013
Last Change:   08/22/2025 Job End Date:   05/28/2014
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   GANITIS, PHILLIP       On     02/06/2014      
Field Disp:   A - OBJCTN ISSD: JOB COMPLETE
Energize Recommendation:  
Objection Disposition:  

License #: 012538 Licensee Name: PAUL J MCTIERNAN
Firm: 004358 Firm Name: PHASEPOINT ELECTL CONTG I
Firm Phone: 718-418-0080  Firm Address: 538 WORTMAN AVENUE BROOKLYN NY 11208 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
L - LIGHTING WORK
Total Fee:  $291.50
Hurricane Sandy Damage:   No
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   Yes
Job Number:  140078314
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: TERRENCE LOWENBERG
Owner Business Name: SMICON REALTY MANAGE LLC
Authorized Representative:  PAUL MCTIERNAN
Relationship To Owner:   SUBCONTRACTOR


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  6  6 SETS OF 3 #4AWG THHN
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  6  6 - 20 CIRCUITS PANELS
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
002  _3  16  16             
002  15  17             
004  _14  15  18             
006  ___24  21  23             
006  __22  17  18             
006  __25  16  17             
Buildings Total 33  100  13  41  109                
Total Units : 296 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice: 1 - FIRST NOTICE 02/20/2014
Power Issued: Response:  

Follow-Up:
Contractor's Comments:  GENERAL WIRING FOR POWER AND LIGHTING BRANCH CIRCUITS

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M341458
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 02/06/2014 02/20/2014 PHG A (80) (6) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M341458
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (282) MINIMUM NUMBER OF SMALL APPLIANCE CIRCUITS
APT.25: ONLY 1 CKT FOR KITCHEN COUNTER TOP. 210.52
OPEN 02/06/2014 02/06/2014
 
002 (282) MINIMUM NUMBER OF SMALL APPLIANCE CIRCUITS
APT.14: NO KITCHEN CKT FOR COUNTER TOP. 210.52
OPEN 02/06/2014 02/06/2014
 
003 (340) RECEPTACLES NOT TAMPERPROOF
APT.3: NO TAMPER FOR A/C RECEPTACLE. 406.11
OPEN 02/06/2014 02/06/2014
 
004 ( 59) AFCI PROTECTION HAS NOT BEEN PROVIDED
APT.24: NO A.F.C.I. FOR HALLWAY RECEPTACLES & LIGHTS. 210.12
OPEN 02/06/2014 02/06/2014
 
005 (340) RECEPTACLES NOT TAMPERPROOF
APT.2: NO TAMPER FOR MICROWAVE REC. 517.18
OPEN 02/06/2014 02/06/2014
 
006 ( 59) AFCI PROTECTION HAS NOT BEEN PROVIDED
APT.2: NO A.F.C.I.FOR HALLWAY RECEPTACLES & CLOSET. 210.12
OPEN 02/06/2014 02/06/2014



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Applications  |  After Hours Variance Permits  |  Electrical Inspection Work Order  |  Back