BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M341032
Premises: 328 SPRING STREET MANHATTAN BIN: 1087495     Block: 595   Lot: 7504
   
Application Completed and Certified

Filed: 334 SPRING ST Census Tract:   37 Health Area:  6800
FIRST FLOOR Admin Area:   M - MANHATTAN Inspection Area:   U
NEW YORK, NY 10013 Community Board:   102
Special Place Name:   PRINT PROMOTION
DOB Cross Street(s):   GREENWICH STREET,    WASHINGTON STREET
Status:   C - JOB IS SIGNED OFF 10/23/2013
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  05/30/2013 5:04 PM
Application Entered:   05/30/2013 Job Start Date:   06/03/2013
Last Change:   10/23/2013 Job End Date:   08/30/2013
Appointment Status:   
Last Inspection By:   ROGALEWSKI, M       On     10/18/2013      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010725 Licensee Name: ALDO BLASKOVIC
Firm: 001917 Firm Name: BLASKO ELECT'L CONTRS INC
Firm Phone: 718-784-7525  Firm Address: 36-38 35TH STREET LONG ISLAND CITY NY 11106 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $318.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   K - Store
Store / Other:   PRINT PROMOTION
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: GLEN AZARIAN
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  1  3/0
D. Over 250 MCM  1  350 MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  
D. 3 Phase Over 225 AMPS  1  400A PANEL
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001    40  45    15  40         
Buildings Total 40  45    15  40              
Total Units : 144 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 10/16/2013
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M341032
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 10/11/2013 10/16/2013 IOS A (55) (8) Y
INSPECTION COMMENTS: WORK PERFORMED ON 1ST FLOOR AND BASEMENT
 
(2) 10/18/2013 10/21/2013 MIR C R (20) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M341032
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
1ST FLOOR: OPEN KOS IN PANELS
RSLV 10/11/2013 10/11/2013 10/18/2013
 
002 (999) OTHER
1ST FLOOR: 2 WIRES UNDER 1 LUG IN PANELS,NEUTRALS AND GROUNDS110.14(A)
RSLV 10/11/2013 10/11/2013 10/18/2013
 
003 (999) OTHER
1ST FLOOR: 10 AWG CONDUCTORS TAPED GREEN. 250.119
RSLV 10/11/2013 10/11/2013 10/18/2013
 
004 (999) OTHER
GROUND BARS MOUNTED WITH SELF TAPPING SCREWS IN PANELS THROUGH-OUT110.2
RSLV 10/11/2013 10/11/2013 10/18/2013
 
005 (999) OTHER
1ST FLOOR: FLEXIBLE CORDS FEEDING LIGHTS ARE NOT SUPPORTED. 334.30
RSLV 10/11/2013 10/11/2013 10/18/2013
 
006 (999) OTHER
1ST FLOOR: E.G.C.UNDERSIZED FOR 2 60A DISCONNECTS. 250.122
RSLV 10/11/2013 10/11/2013 10/18/2013
 
007 (999) OTHER
BSMT: BUSHING REQUIRED IN DISCONNECT. 314.17(B)
RSLV 10/11/2013 10/11/2013 10/18/2013
 
008 ( 21) CONDUCTORS HAVE NOT BEEN PROPERLY DE-RATED
BSMT: CONDUCTORS NEED DERATING IN 200A PANEL
RSLV 10/11/2013 10/11/2013 10/18/2013