| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
1 |
3/0 |
| D. Over 250 MCM |
1 |
350 MCM |
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
1 |
|
| D. 3 Phase Over 225 AMPS |
1 |
400A PANEL |
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 34) |
KNOCKOUTS ARE NOT CLOSED IN PANEL BOX 1ST FLOOR: OPEN KOS IN PANELS |
RSLV |
10/11/2013 |
10/11/2013 |
10/18/2013 |
| |
| 002 |
(999) |
OTHER 1ST FLOOR: 2 WIRES UNDER 1 LUG IN PANELS,NEUTRALS AND GROUNDS110.14(A) |
RSLV |
10/11/2013 |
10/11/2013 |
10/18/2013 |
| |
| 003 |
(999) |
OTHER 1ST FLOOR: 10 AWG CONDUCTORS TAPED GREEN. 250.119 |
RSLV |
10/11/2013 |
10/11/2013 |
10/18/2013 |
| |
| 004 |
(999) |
OTHER GROUND BARS MOUNTED WITH SELF TAPPING SCREWS IN PANELS THROUGH-OUT110.2 |
RSLV |
10/11/2013 |
10/11/2013 |
10/18/2013 |
| |
| 005 |
(999) |
OTHER 1ST FLOOR: FLEXIBLE CORDS FEEDING LIGHTS ARE NOT SUPPORTED. 334.30 |
RSLV |
10/11/2013 |
10/11/2013 |
10/18/2013 |
| |
| 006 |
(999) |
OTHER 1ST FLOOR: E.G.C.UNDERSIZED FOR 2 60A DISCONNECTS. 250.122 |
RSLV |
10/11/2013 |
10/11/2013 |
10/18/2013 |
| |
| 007 |
(999) |
OTHER BSMT: BUSHING REQUIRED IN DISCONNECT. 314.17(B) |
RSLV |
10/11/2013 |
10/11/2013 |
10/18/2013 |
| |
| 008 |
( 21) |
CONDUCTORS HAVE NOT BEEN PROPERLY DE-RATED BSMT: CONDUCTORS NEED DERATING IN 200A PANEL |
RSLV |
10/11/2013 |
10/11/2013 |
10/18/2013 |