BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M340975
Premises: 39 WORTH STREET MANHATTAN BIN: 1001961     Block: 176   Lot: 11
   
Application Completed and Certified

Filed: 39 WORTH ST Census Tract:   33 Health Area:  7700
APT 4E Admin Area:   M - MANHATTAN Inspection Area:   W
NEW YORK, NY 10013 Community Board:   101
DOB Cross Street(s):   WEST BROADWAY,    CHURCH STREET
Status:   C - JOB IS SIGNED OFF 10/24/2013
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  05/29/2013 4:40 PM
Application Entered:   05/29/2013 Job Start Date:   05/29/2013
Last Change:   10/24/2013 Job End Date:   06/15/2013
Appointment Status:   
Last Inspection By:   HUGH MCKESSEY       On     10/17/2013      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 009113 Licensee Name: MARTIN WEINSTEIN
Firm: 000796 Firm Name: JOSEPH WEINSTEIN ELECTRIC
Firm Phone: 718-843-5555  Firm Address: 94-24 88TH STREET CORP OZONE PARK NY 11416 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $43.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: MARK GOLDMAN
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
004                   
Buildings Total                   
Total Units : 22 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 10/04/2013
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M340975
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 08/20/2013 08/27/2013 LBI A (40) (3) Y
INSPECTION COMMENTS: **SEE OBJECTIONS
 
(2) 09/23/2013 10/04/2013 EDB A Y (40) (1) Y
INSPECTION COMMENTS: NONE
 
(3) 10/17/2013 10/21/2013 HMC C R (15) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M340975
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (272) EQUIPMENT GROUNDING CONDUCTOR NOT PROPERLY INSTALLED
4E: TOWEL WARM & FLOOR HEAT CKTS NOT GROUNDED RE:GREENFIELD FROM PNL- 250.118
RSLV 08/20/2013 09/23/2013 10/17/2013
 
002 (114) GFCI HAS NOT BEEN PROVIDED FOR BATHROOM RECEPTACLES
4E: POWDER ROOM RECEPTACLE BEHIND SINK NOT G.F.C.I.PROTECTED- 210.8A1
RSLV 08/20/2013 08/20/2013 09/23/2013
 
003 (999) OTHER
4E: BOND WIRE FROM COPPER WATER PIPE MOTOR FRAME UNDERSIZED- 680.73
RSLV 08/20/2013 08/20/2013 09/23/2013
 
004 (999) OTHER
PANEL: MULTIWIRE CKT NO GROUPED,NO SIMULT TRIP. 210.4
RSLV 09/23/2013 09/23/2013 10/17/2013



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.