| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
1 |
200A, S.S. |
| C. 201 Up to 600 AMPS |
2 |
400A. S.S. |
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
1 |
3/0 WIRE |
| D. Over 250 MCM |
2 |
500 MCM |
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
15 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
7 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(129) |
SERVICE SWITCH NEUTRAL NOT BONDED TO ENCLOSURE (ALL FLOORS) EL RM: 200A SER.SW NEUTRAL NOT BND/GND. 250.28 |
RSLV |
10/14/2014 |
10/14/2014 |
06/27/2017 |
| |
| 002 |
(999) |
OTHER (ALL FLOORS) EL.RM: EGC FOR 400A FEEDERS NOT SIZED AS PER 250.122 |
RSLV |
10/14/2014 |
10/14/2014 |
06/27/2017 |
| |
| 003 |
(279) |
WATER METER JUMPER IS MISSING/IMPROPER (ALL FLOORS) EL RM: WATER METER NOT BND. 250.53 |
RSLV |
10/14/2014 |
10/14/2014 |
06/27/2017 |
| |
| 004 |
( 14) |
CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE (ALL FLOORS) EL RM: #4 RISER FUSED AT 100A FOR APT.14. 240.3 |
RSLV |
10/14/2014 |
10/14/2014 |
06/27/2017 |
| |
| 005 |
(243) |
CONDUCTORS OF THE SAME CIRCUIT NOT GROUPED (ALL FLOORS)EL.RM: NO NEUTRALS RAN WITH FEEDERS TO APT 9A,9B,9C AT DISC. 300.3(B |
RSLV |
10/14/2014 |
10/14/2014 |
06/27/2017 |
| |
| 006 |
(128) |
NEUTRAL IS GROUNDED BEYOND LOAD SIDE OF SERVICE SWITCH (ALL FLOORS) EL.RM: ELEV NEUTRAL BND AFTER SER SW. 250.24(A5) |
RSLV |
10/14/2014 |
10/14/2014 |
06/27/2017 |
| |
| 007 |
(999) |
OTHER (ALL FLOORS) EL.RM: ELEV NEUTRAL NOT SIZED AS PER 250.122 |
RSLV |
10/14/2014 |
10/14/2014 |
06/27/2017 |
| |
| 008 |
( 25) |
ARMORED CABLES ARE NOT PROPERLY TERMINATED (ALL FLOORS) EL.RM: ARMORED CABLES NOT PROPERLY TERM. 320.40 |
RSLV |
10/14/2014 |
10/14/2014 |
06/27/2017 |
| |
| 009 |
( 1) |
SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER (ALL FLOORS) EL.RM: RACEWAY NOT BND TO ENC.AT SERVICE ENTRY. 250.92 |
RSLV |
10/14/2014 |
10/14/2014 |
06/27/2017 |
| |
| 010 |
(999) |
OTHER (FLOOR: 001)NO ILLUMINATION PROVIDED IN ELECTRICAL ROOM. NEC 110.26 |
RSLV |
06/27/2017 |
06/27/2017 |
09/25/2017 |
| |
| 011 |
(999) |
OTHER (FLOOR: 001)EQUIPMENT, PANELS NOT GROUNDED .NO EQUIPMENT GROUNDING CONDUCTORSUSED IN FMC FOR RACEWAYS TO APARTMENTS 1C, 9A, 9B, 9C AND PLP |
RSLV |
06/27/2017 |
06/27/2017 |
09/25/2017 |
| |
| 012 |
( 34) |
KNOCKOUTS ARE NOT CLOSED IN PANEL BOX (BASEMENT) PANELS AND METER BANK BLANKS MISSING. |
RSLV |
09/05/2017 |
09/05/2017 |
09/25/2017 |
| |
| 013 |
(999) |
OTHER (BASEMENT) WATER JUMPER UNDER SIZE 250.66 |
RSLV |
09/05/2017 |
09/05/2017 |
09/25/2017 |