| BUILDING OVERVIEW |
Are Feeders Being Installed? : No |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(272) |
EQUIPMENT GROUNDING CONDUCTOR NOT PROPERLY INSTALLED 1FL: SUB. PANEL: MC CABLE GROUNDS NOT TERMINATED. 250.10, 408.40 |
RSLV |
08/30/2013 |
08/30/2013 |
12/02/2013 |
| |
| 002 |
(999) |
OTHER 1FL: BOTH PANELS: HANDLE TIES NOT PROVIDED FOR 3 WIRE CKTS. 210.4B |
OPEN |
08/30/2013 |
12/02/2013 |
|
| |
| 003 |
(999) |
OTHER 1FL: MAIN PANEL: 3 WIRE BOX IN DUAL CONNECTOR NOT GROUPED PER 210.4D |
OPEN |
08/30/2013 |
12/02/2013 |
|
| |
| 004 |
(211) |
RECEPTACLE IS NOT PROPERLY BONDED/GROUNDED 1FL: FRIDGE RECEPTACLE IN CLOSET NOT GROUNDED / BONDED. 250.146 |
OPEN |
08/30/2013 |
12/02/2013 |
|
| |
| 005 |
( 29) |
OUTLET BOXES ARE NOT COVERED 1FL: FRIDGE RECEPTACLE IN CLOSET NOT COVERED. 314.25 |
OPEN |
08/30/2013 |
12/02/2013 |
|
| |
| 006 |
( 53) |
GFCI HAS NOT BEEN PROVIDED 1FL: BEHIND COUNTER: RECEPTACLES WITHIN 6' OF SINK NOT GFCIPROTECTED. 210.B5 |
RSLV |
08/30/2013 |
08/30/2013 |
12/02/2013 |
| |
| 007 |
( 22) |
FIXED EQUIPMENT IS NOT PROPERLY GROUNDED 1FL: WALK-IN FAN AND LIGHT NOT GROUNDED / NOT BONDED TO J-BOX FEDWITH BX. 250.110, 250.148 |
OPEN |
08/30/2013 |
12/02/2013 |
|
| |
| 008 |
( 46) |
PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY 1FL: PANEL DIRECTORIES ARE NOT COMPLETE. 408.4 |
RSLV |
08/30/2013 |
08/30/2013 |
12/02/2013 |
| |
| 009 |
( 34) |
KNOCKOUTS ARE NOT CLOSED IN PANEL BOX PANEL |
OPEN |
12/02/2013 |
12/02/2013 |
|
| |
| 010 |
( 25) |
ARMORED CABLES ARE NOT PROPERLY TERMINATED PANEL |
OPEN |
12/02/2013 |
12/02/2013 |
|
| |
| 011 |
( 19) |
DEFECTIVE WIRING IS IN USE REAR ROOM: WALKIN REFRIGERATOR - NOT METALLIC LFC IN USE |
OPEN |
12/02/2013 |
12/02/2013 |
|
| |
| 012 |
( 24) |
ARMORED CABLES ARE NOT PROPERLY SECURED REAR ROOM: ABOVE WALKIN REFRIGERATOR |
OPEN |
12/02/2013 |
12/02/2013 |
|
| |
| 013 |
( 19) |
DEFECTIVE WIRING IS IN USE REAR ROOM: LFC PASSES THROUGH STRUCTURE OF WALKIN REFEIGERATOR |
OPEN |
12/02/2013 |
12/02/2013 |
|
| |
| 014 |
( 19) |
DEFECTIVE WIRING IS IN USE REAR ROOM: NO DISCONNECT FOR REFRIGERATION UNIT INSIDE WALKIN BOX |
OPEN |
12/02/2013 |
12/02/2013 |
|