Electrical Application Details for App #: M340476
Premises: 120 2 AVENUE MANHATTAN BIN: 1006308     Block: 449   Lot: 2
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 120 2 AV Census Tract:   38 Health Area:  6500
1FLR/BSMT Admin Area:   M - MANHATTAN Inspection Area:   T
NEW YORK, NY 10003 Community Board:   103
DOB Cross Street(s):   EAST 7 STREET,    ST MARKS PLACE
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  05/15/2013 5:16 PM
Application Entered:   05/15/2013 Job Start Date:   05/16/2013
Last Change:   08/22/2025 Job End Date:   05/16/2014
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   MOSES, DANIEM       On     05/01/2014      
Field Disp:   N - NO ACCESS
Energize Recommendation:  
Objection Disposition:  Y - PARTLY REMOVED

License #: 010985 Licensee Name: LINDEN J TUDOR
Firm: 002700 Firm Name: LINTECH ELECTRIC, INC
Firm Phone: 718-941-3766  Firm Address: 3006 TILDEN AVENUE BROOKLYN NY 11226 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $73.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   K - Store
Store / Other:   YOGURT SHOP
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: RICHARD ALFONSO
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS    10  10    10               
001    70  25    20               
Buildings Total 80  35    30                  
Total Units : 145 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice: 1 - FIRST NOTICE 12/17/2013
Power Issued: Response:  

Follow-Up:
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M340476
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 08/30/2013 09/05/2013 LBI A (45) (8) Y
INSPECTION COMMENTS: WORK PERFORMED ON 1FL ONLY
 
(2) 09/25/2013 10/05/2013 JKF N (40) (0) Y
INSPECTION COMMENTS: STORE CLOSED CONTRACTOR NOT ON SITE
 
(3) 11/14/2013 11/21/2013 NRS N (15) (0) Y
INSPECTION COMMENTS: NONE
 
(4) 12/02/2013 12/17/2013 JKF A Y (35) (6) Y
INSPECTION COMMENTS: 004,005 UNKNOWN LOCATIONS
 
(5) 02/13/2014 02/28/2014 EDB Z (0) (0) Y
INSPECTION COMMENTS: CANCEL WITH OFFICE
 
(6) 02/26/2014 03/11/2014 IOS N (25) (0) Y
INSPECTION COMMENTS: CONTRACTOR UNWARE OF INSPECTION
 
(7) 03/12/2014 03/22/2014 TOR N (30) (0) Y
INSPECTION COMMENTS: CALLED CONTRACTOR ON THE WAY,NO SHOW
 
(8) 05/01/2014 05/16/2014 DNM N (20) (0) Y
INSPECTION COMMENTS: NO SHOW

OBJECTION FOR APPLICATION #: M340476
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (272) EQUIPMENT GROUNDING CONDUCTOR NOT PROPERLY INSTALLED
1FL: SUB. PANEL: MC CABLE GROUNDS NOT TERMINATED. 250.10, 408.40
RSLV 08/30/2013 08/30/2013 12/02/2013
 
002 (999) OTHER
1FL: BOTH PANELS: HANDLE TIES NOT PROVIDED FOR 3 WIRE CKTS. 210.4B
OPEN 08/30/2013 12/02/2013
 
003 (999) OTHER
1FL: MAIN PANEL: 3 WIRE BOX IN DUAL CONNECTOR NOT GROUPED PER 210.4D
OPEN 08/30/2013 12/02/2013
 
004 (211) RECEPTACLE IS NOT PROPERLY BONDED/GROUNDED
1FL: FRIDGE RECEPTACLE IN CLOSET NOT GROUNDED / BONDED. 250.146
OPEN 08/30/2013 12/02/2013
 
005 ( 29) OUTLET BOXES ARE NOT COVERED
1FL: FRIDGE RECEPTACLE IN CLOSET NOT COVERED. 314.25
OPEN 08/30/2013 12/02/2013
 
006 ( 53) GFCI HAS NOT BEEN PROVIDED
1FL: BEHIND COUNTER: RECEPTACLES WITHIN 6' OF SINK NOT GFCIPROTECTED. 210.B5
RSLV 08/30/2013 08/30/2013 12/02/2013
 
007 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
1FL: WALK-IN FAN AND LIGHT NOT GROUNDED / NOT BONDED TO J-BOX FEDWITH BX. 250.110, 250.148
OPEN 08/30/2013 12/02/2013
 
008 ( 46) PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY
1FL: PANEL DIRECTORIES ARE NOT COMPLETE. 408.4
RSLV 08/30/2013 08/30/2013 12/02/2013
 
009 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
PANEL
OPEN 12/02/2013 12/02/2013
 
010 ( 25) ARMORED CABLES ARE NOT PROPERLY TERMINATED
PANEL
OPEN 12/02/2013 12/02/2013
 
011 ( 19) DEFECTIVE WIRING IS IN USE
REAR ROOM: WALKIN REFRIGERATOR - NOT METALLIC LFC IN USE
OPEN 12/02/2013 12/02/2013
 
012 ( 24) ARMORED CABLES ARE NOT PROPERLY SECURED
REAR ROOM: ABOVE WALKIN REFRIGERATOR
OPEN 12/02/2013 12/02/2013
 
013 ( 19) DEFECTIVE WIRING IS IN USE
REAR ROOM: LFC PASSES THROUGH STRUCTURE OF WALKIN REFEIGERATOR
OPEN 12/02/2013 12/02/2013
 
014 ( 19) DEFECTIVE WIRING IS IN USE
REAR ROOM: NO DISCONNECT FOR REFRIGERATION UNIT INSIDE WALKIN BOX
OPEN 12/02/2013 12/02/2013