BIS Menu  |  Applications  |  Plumb. Inspections  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M340298
Premises: 301 EAST 68 STREET MANHATTAN BIN: 1044753     Block: 1443   Lot: 1
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 315 E 68 ST Census Tract:   118 Health Area:  4400
3A Admin Area:   M - MANHATTAN Inspection Area:   K
NEW YORK, NY 10065 Community Board:   108
DOB Cross Street(s):    2 AVENUE,    1 AVENUE
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  05/10/2013 1:54 PM
Application Entered:   05/10/2013 Job Start Date:   05/10/2013
Last Change:   08/22/2025 Job End Date:   12/30/2013
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   GANITIS, PHILLIP       On     12/18/2013      
Field Disp:   A - OBJCTN ISSD: JOB COMPLETE
Energize Recommendation:  
Objection Disposition:  

License #: 011175 Licensee Name: DONALD MCGEACHY
Firm: 000436 Firm Name: DONALD MCGEACHY, INC.
Firm Phone: 212-249-0999  Firm Address: 502A EAST 84 STREET NEW YORK NY 10028 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $44.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: CHARLENE GIBBS
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
003  3A             
Buildings Total               
Total Units : 27 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice: 1 - FIRST NOTICE 12/30/2013
Power Issued: Response:  

Follow-Up:
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M340298
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 12/09/2013 12/09/2013 PHG N (20) (0) Y
INSPECTION COMMENTS: NO SHOW
 
(2) 12/09/2013 12/14/2013 PHG N (25) (0) Y
INSPECTION COMMENTS: CONTRACTOR DID NOT SHOW UP
 
(3) 12/18/2013 12/30/2013 PHG A (55) (3) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M340298
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 11) FEEDER CONDUCTORS ARE NOT OF PROPER SIZE
PANNEL FEEDER IS TOO SMALL PANNEL FED WITH # 10 WIRE AM. 215.2
OPEN 12/18/2013 12/18/2013
 
002 (211) RECEPTACLE IS NOT PROPERLY BONDED/GROUNDED
3A REEPLES NOT GROUDED 250.146
OPEN 12/18/2013 12/18/2013
 
003 ( 14) CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE
BSMT FEEDER FUSED TOO HIGH # 10 WIRE OR 35 AMP FUSE 240.3
OPEN 12/18/2013 12/18/2013



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.