BIS Menu  |  Plumb. Inspections  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M339351
Premises: 82 UNIVERSITY PLACE MANHATTAN BIN: 1009286     Block: 569   Lot: 7505
   
Application Completed and Certified

Filed: 82 UNIVERSITY PL Census Tract:   61 Health Area:  5700
82 UNIVERSIY PLACE Admin Area:   M - MANHATTAN Inspection Area:   S
NEW YORK, NY 10003 Community Board:   102
Special Place Name:   EUROPEAN WAX
DOB Cross Street(s):   EAST 11 STREET,    EAST 12 STREET
Status:   C - JOB IS SIGNED OFF 11/14/2013
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  04/18/2013 2:03 PM
Application Entered:   04/18/2013 Job Start Date:   04/18/2013
Last Change:   11/14/2013 Job End Date:   08/30/2013
Appointment Status:   
Last Inspection By:   BEST, J       On     10/08/2013      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011850 Licensee Name: JAMES P ST. JOHN
Firm: 003455 Firm Name: PATRIOT ELECTRIC CORP
Firm Phone: 718-736-8733  Firm Address: 15-17 126TH STREET 3RD FLOOR COLLEGE POINT NY 11356 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $106.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   K - Store
Store / Other:   RETAIL
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: JOSPEH BASILE
Owner Business Name: JFB CONSTRUCTION
Authorized Representative:  JOSEPH BASILE
Relationship To Owner:   OWNERS REP


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  6  30AMP 3 PHASE
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
GND    55  27                 
Buildings Total 55  27                    
Total Units : 84 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 08/06/2013
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  INSTALLATION OF LIGHTING, RECPETACLES AND SWITCHES PANEL EXISITING

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M339351
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 07/31/2013 08/06/2013 LBI A (35) (2) Y
INSPECTION COMMENTS: **SEE OBJECTIONS
 
(2) 10/08/2013 10/10/2013 JSB C R (30) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M339351
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (272) EQUIPMENT GROUNDING CONDUCTOR NOT PROPERLY INSTALLED
1FL: EGC UNDERSIZED FOR ALL MECH EQUIP-PANEL EP1A... - TAB 250.122
RSLV 07/31/2013 07/31/2013 10/08/2013
 
002 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
1FL: BREAKER BLANKS MISSING PANEL EP-1...... - 110.12A
RSLV 07/31/2013 07/31/2013 10/08/2013



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.