BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M338669
Premises: 145 GREENE STREET MANHATTAN BIN: 1086553     Block: 514   Lot: 7505
   
Application Completed and Certified

Filed: 158 WOOSTER ST Census Tract:   49 Health Area:  6800
GROUND FLOOR Admin Area:   M - MANHATTAN Inspection Area:   U
NEW YORK, NY 10012 Community Board:   102
DOB Cross Street(s):   PRINCE STREET,    WEST HOUSTON STREET
Status:   C - JOB IS SIGNED OFF 08/06/2013
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  04/01/2013 10:11 PM
Application Entered:   04/01/2013 Job Start Date:   04/01/2013
Last Change:   08/06/2013 Job End Date:   05/29/2013
Appointment Status:   
Last Inspection By:   GARY MCCALLA       On     07/18/2013      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010593 Licensee Name: JOSE A MARENGO
Firm: 002839 Firm Name: ECS ELEC'L CONTG SERV INC
Firm Phone: 718-484-8884  Firm Address: 435 AUSTIN PLACE, SUITE E BRONX NY 10455 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $116.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Other
Store / Other:   RETAIL SHOWROOM
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: JR COLLASSO
Owner Business Name: BULTHAUP SHOWROOM
Authorized Representative:  JR COLLASSO
Relationship To Owner:   PROJECT MANAGER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  4# 2AWG
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  100AMP 3PHASE
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
GND    10  18    22             
Buildings Total 10  18    22                
Total Units : 56 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 07/03/2013
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M338669
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 06/24/2013 07/03/2013 IOS A (60) (7) Y
INSPECTION COMMENTS: **SEE OBJECTIONS
 
(2) 07/18/2013 07/27/2013 GYM C R (40) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M338669
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
MULTICIRCUITS NOT ON SINGLE TIE BREAKER..... - 210.4(B)
RSLV 06/24/2013 06/24/2013 07/18/2013
 
002 ( 16) DEFECTIVE LIGHTING FIXTURES ARE IN USE
EXIT SIGN IN BASEMENT NOT WORKING PROPERLY
RSLV 06/24/2013 06/24/2013 07/18/2013
 
003 ( 46) PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY
PANEL DIRECTORY IS INCORRECTLY LABELED
RSLV 06/24/2013 06/24/2013 07/18/2013
 
004 (999) OTHER
RECEPTACLE ON WALL NEXT TO SINK NOT G.F.C.I.WITHIN 6'.... - 210.8
RSLV 06/24/2013 06/24/2013 07/18/2013
 
005 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
SHEETROCK SCREWS USED ON RECEPTACLES
RSLV 06/24/2013 06/24/2013 07/18/2013
 
006 (999) OTHER
RECEPTACLES NOT BONDED THROUGH-OUT..... - 210.146
RSLV 06/24/2013 06/24/2013 07/18/2013
 
007 ( 16) DEFECTIVE LIGHTING FIXTURES ARE IN USE
EXIT SIGN BY SIDE DOOR AND NOT FRONT DOOR WORKING
RSLV 06/24/2013 06/24/2013 07/18/2013



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.