BIS Menu  |  Pre-BIS PA CO Query By Bin  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M338665
Premises: 236 FRONT STREET MANHATTAN BIN: 1087577     Block: 97   Lot: 32
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 24 PECK SLIP Census Tract:   15.01 Health Area:  7700
24 Admin Area:   M - MANHATTAN Inspection Area:   W
NEW YORK, NY 10038 Community Board:   101
DOB Cross Street(s):   WATER STREET,    FRONT STREET
Status:   C - JOB IS SIGNED OFF 11/13/2020
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  04/01/2013 7:35 PM
Application Entered:   04/01/2013 Job Start Date:   04/02/2013
Last Change:   11/13/2020 Job End Date:   04/02/2016
Appointment Status:   
Last Inspection By:   VAZQUEZ, LOUIS       On     11/13/2020      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011765 Licensee Name: RADOS MILOJKOVIC
Firm: 003122 Firm Name: CENTENNIAL ELEVATOR INDUS
Firm Phone: 718-726-5900  Firm Address: 24-35 47TH STREET ASTORIA NY 11103 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
3 - ELEVATOR/ESCALATOR/MATERIAL LIFT
Total Fee:  $165.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: TIMOTHY CONSOLO
Owner Business Name: HISTORIC FRONT PRO
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  1  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 10/20/2014
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M338665
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 10/10/2014 10/20/2014 TOR A (20) (3) Y
INSPECTION COMMENTS: #1P43344 MOTOR EXISTING
 
(2) 11/13/2020 11/13/2020 LV1 C R (20) (0)
INSPECTION COMMENTS: PASS

OBJECTION FOR APPLICATION #: M338665
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 19) DEFECTIVE WIRING IS IN USE
(ALL FLOORS) MACH.ROOM: NEUTRAL FUSED (CAB LIGHT DISCONNECT)
RSLV 10/10/2014 10/10/2014 11/13/2020
 
002 (186) 125V, 15/20AMP RECEPTICAL IN MACHINE AREA NOT GFCI
(ALL FLOORS) MECH.ROOM: ROOF NO G.F.C.I.FOR ELEVATOR ROOM
RSLV 10/10/2014 10/10/2014 11/13/2020
 
003 (999) OTHER
(ALL FLOORS)MECH ROOM. ROOF MAIN DISCONNECT & CONTROLLER 2 GROUND WIRES UNDERONE LUG. 110.14(A)
RSLV 10/10/2014 10/10/2014 11/13/2020



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.