BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M337692
Premises: 226 LAFAYETTE STREET MANHATTAN BIN: 1007216     Block: 482   Lot: 22
   
Application Completed and Certified

Filed: 226 LAFAYETTE ST Census Tract:   45 Health Area:  6800
BASEMENT Admin Area:   M - MANHATTAN Inspection Area:   U
NEW YORK, NY 10012 Community Board:   102
DOB Cross Street(s):   KENMARE STREET,    CLEVELAND PLACE
Status:   C - JOB IS SIGNED OFF 06/04/2015
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  03/07/2013 11:14 AM
Application Entered:   03/07/2013 Job Start Date:   03/07/2013
Last Change:   06/04/2015 Job End Date:   03/06/2014
Appointment Status:   
Last Inspection By:   RAMJAG, BUDRAM       On     05/29/2015      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 012196 Licensee Name: ANTHONY NOLAN
Firm: 003904 Firm Name: ALLCOM ELECTRIC CORP
Firm Phone: 718-402-2481  Firm Address: 243 EAST 138TH STREET BRONX NY 10451 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
Total Fee:  $790.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Commercial/Residential (1  Stores, 6 Apartments)
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: 226 LAFAYETTE COMPANY INC
Authorized Representative:  EVELYN WASSMAN
Relationship To Owner:   MANAGER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  1  1600
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  4  600KCMIL
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  1  1600AMP DISTRIBUTION
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 1 #10-Wire 0
Existing Meters 8 + New Meters 1 - Removed Meters 1 = Total Meters 8

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 03/07/2013 Notice: 1 - FIRST NOTICE 11/17/2014
Power Issued: 03/07/2013 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M337692
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 11/06/2014 11/17/2014 FRI A E (90) (3) Y
INSPECTION COMMENTS: NONE
 
(2) 05/29/2015 06/04/2015 BUR C R E (35) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M337692
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
SVC.SW: SUPPLEMENTAL GND COND.NOT CONNECTED TO NEUTRAL
RSLV 11/06/2014 11/06/2014 05/29/2015
 
002 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
SVC.SW: ENDLINE DETAIL BOX NOT PROPERLY BONDED TO SVC.SW
RSLV 11/06/2014 11/06/2014 05/29/2015
 
003 (999) OTHER
SVC.SW: SEC NOT PROPERLY PROTECTED FROM SHARP EDGES OF CUT-OUT300.4G
RSLV 11/06/2014 11/06/2014 05/29/2015



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order