Electrical Application Details for App #: M337555
Premises: 15 WILLIAM STREET MANHATTAN BIN: 1087954     Block: 25   Lot: 7501
   
Application Completed and Certified

Filed: 15 WILLIAM ST Census Tract:   9 Health Area:  7700
GROUND FLOOR Admin Area:   M - MANHATTAN Inspection Area:   W
NEW YORK, NY 10004 Community Board:   101
Special Place Name:   OPEN KITCHEN
DOB Cross Street(s):   BEAVER STREET,    EXCHANGE PLACE
Status:   C - JOB IS SIGNED OFF 04/01/2014
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  03/04/2013 11:21 PM
Application Entered:   03/04/2013 Job Start Date:   03/05/2013
Last Change:   04/01/2014 Job End Date:   05/15/2013
Appointment Status:   
Last Inspection By:   BEST, J       On     03/14/2014      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 009611 Licensee Name: WINSTON BERKEL
Firm: 003336 Firm Name: U.S. ELECTRIC CORP.
Firm Phone: 718-706-1442  Firm Address: 13-07 37TH AVENUE LONG ISLAND CITY NY 11101 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $485.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Other
Store / Other:   DELI
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: OPEN KITCHEN 15 WILLIAM,
Authorized Representative:  ING KIM
Relationship To Owner:   OWNER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  7  5-200AMP & 2=100AMP
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
GND    105  120    10  130  25         
Buildings Total 105  120    10  130     25           
Total Units : 390 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 08/14/2013
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  PANELS AND BRANCH WIRING FOR RECEPTACLES AND LIGHTS.

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M337555
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 08/07/2013 08/14/2013 CLC V (60) (7) Y
INSPECTION COMMENTS: **SEE OBJECTIONS
 
(2) 03/14/2014 03/24/2014 JSB C R (45) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M337555
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
1ST FL: PANEL MULTIWIRE BRANCH CKTS IN USE..... - 210.4
RSLV 08/07/2013 08/07/2013 03/14/2014
 
002 (999) OTHER
1ST FL: TRACK LIGHTING FIX WIRING SHALL BE OF A TYPE LISTED IN TABLE402.3
RSLV 08/07/2013 08/07/2013 03/14/2014
 
003 (999) OTHER
1ST FL: DISHWASHER E.G.C. UNDER SIZE...... - 250.122
RSLV 08/07/2013 08/07/2013 03/14/2014
 
004 ( 9) SQ AREA OF SUM OF CONDUCTORS EXCEEDS SQ AREA FILL OF RACEWAY
1ST FL: KITCHEN CEILING TOO MANY WIRES IN SPLICE BOX
RSLV 08/07/2013 08/07/2013 03/14/2014
 
005 ( 15) FLEXIBLE CORDS USED AS PERMANENT WIRING METHOD
1ST FL: FLEXIBLE CORDS USED TO FEED SALAD BARS
RSLV 08/07/2013 08/07/2013 03/14/2014
 
006 ( 30) OUTLET BOXES ARE NOT SECURED
1ST FL: FRONT DOOR ENT CEILING SPLICE BOX HANGING
RSLV 08/07/2013 08/07/2013 03/14/2014
 
007 ( 19) DEFECTIVE WIRING IS IN USE
1ST FL: OUTDOOR FIXTURES JELLY JARS FEED WITH SJ CORDS
RSLV 08/07/2013 08/07/2013 03/14/2014