BIS Menu  |  Pre-BIS PA CO Query By Bin  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M337429
Premises: 150 EAST 73 STREET MANHATTAN BIN: 1042858     Block: 1407   Lot: 51
   
Application Completed and Certified

Filed: 150 E 73 ST Census Tract:   128 Health Area:  4100
11C Admin Area:   M - MANHATTAN Inspection Area:   K
NEW YORK, NY 10021 Community Board:   108
DOB Cross Street(s):   LEXINGTON AVENUE,    3 AVENUE
Status:   C - JOB IS SIGNED OFF 11/25/2013
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  02/27/2013 10:02 PM
Application Entered:   02/27/2013 Job Start Date:   03/01/2013
Last Change:   11/25/2013 Job End Date:   12/15/2013
Appointment Status:   
Last Inspection By:   MOSES, DANIEM       On     10/22/2013      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011903 Licensee Name: WIESLAW MAKSIM
Firm: 003541 Firm Name: DENMAR ELECTRIC CORP
Firm Phone: 718-533-6753  Firm Address: 5 PENN PLAZA 19TH FLOOR NEW YORK NY 10001 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $97.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: JOHN WILKINS
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  1  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
011  11C  20  35  14  20             
Buildings Total 20  35  14  20                
Total Units : 91 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 10/05/2013
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M337429
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 09/25/2013 10/05/2013 LBI A (30) (6) Y
INSPECTION COMMENTS: NONE
 
(2) 10/22/2013 10/30/2013 DNM C R (20) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M337429
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (128) NEUTRAL IS GROUNDED BEYOND LOAD SIDE OF SERVICE SWITCH
11C: NEUTRAL BONDED IN NEW PANEL. 250.24A5
RSLV 09/25/2013 09/25/2013 10/22/2013
 
002 (999) OTHER
11C: NO BREAKER HANDLE TIES PROVIDED FOR MULTIWIRE CKTS(PANEL)210.4B
RSLV 09/25/2013 09/25/2013 10/22/2013
 
003 (282) MINIMUM NUMBER OF SMALL APPLIANCE CIRCUITS
11C: ALL KITCHEN COUNTER RECEPTACLES SERVED BY ONE CIRCUIT210.11,250.52B1
RSLV 09/25/2013 09/25/2013 10/22/2013
 
004 ( 59) AFCI PROTECTION HAS NOT BEEN PROVIDED
11C: NO A.F.C.I.PROVIDED FOR HALL,BEDROOM AND ALL CLOSET LIGHTS210.12B
RSLV 09/25/2013 09/25/2013 10/22/2013
 
005 (999) OTHER
11C: INCANDESCENT FIXTURES WITH OPEN LAMPS NOT PERMITTED FOR CLOTHESCLOSETS. 410.16B
RSLV 09/25/2013 09/25/2013 10/22/2013
 
006 (999) OTHER
11C: KITCHEN PLUGMOLD NOT TAMPER RESISTANT TYPE. 406.11
RSLV 09/25/2013 09/25/2013 10/22/2013



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Pre-BIS PA CO Query By Bin  |  Electrical Inspection Work Order  |  Back