BIS Menu  |  Plumb. Inspections  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M337321
Premises: 150 WEST 10 STREET MANHATTAN BIN: 1010679     Block: 610   Lot: 42
   

DOB NOW: Inspections


Filed: 181 WAVERLY PL Census Tract:   71
APT 3F Admin Area:   M - MANHATTAN Inspection Area:   R
NEW YORK, NY 10014 Community Board:   102
Special Place Name:   3RD FLOOR APT 3F
DOB Cross Street(s):   CHRISTOPHER STREET,    WEST 10 STREET
Status:   E - ABANDONED 08/22/2025
Request Type:   P - PICK-UP eFiled:   NO
Application Entered:   02/25/2013 Job Start Date:  
Last Change:   08/22/2025 Job End Date:  
Appointment Status:    Complaint Number:    1343703
Last Inspection By:   DORSAINVILLE, R       On     02/22/2013      
Field Disp:   W - ISSUE OBJECTION TO OWNER
Energize Recommendation:  
Objection Disposition:  

License #: Licensee Name: UNKNOWN
Firm: Firm Name: UNKNOWN
Firm Phone:   Firm Address:  

Work Started or Filed by Others: NO
Work Category:    Work To Be Done:   Total Fee:  $0.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   C - Three Family
Special Cert Approval:  
Advisory Board Approval:  
Owner / Occup:
Owner Business Name: JONIS-181 WAVERLY PLACE
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice: 1 - FIRST NOTICE 02/25/2013
Power Issued: Response:  

Follow-Up: V - OWNER OBJECTION 02/25/2013
Contractor's Comments:  THE ENTIRE APT 3F

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M337321
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 02/22/2013 02/25/2013 RID W (15) (7)
INSPECTION COMMENTS: SEE VIOLATION DETAILS

OBJECTION FOR APPLICATION #: M337321
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 3) APPLICATION FOR CERTIFICATE OF ELECTRICAL INSPECTION NOT ON FILE
THE ENTIRE APT 3FCOM: SUB PANEL, BRANCH CIRCUIT WIRING, RECEPT. OUTLETS, SWITCHE, FIX
OPEN 02/22/2013 02/22/2013
 
002 (999) OTHER
SPLICE BOXES NOT ACCESSIBLE. 314.29
OPEN 02/22/2013 02/22/2013
 
003 (999) OTHER
SUB FEEDER UNDER SIZE: 215.2(A)(L)
OPEN 02/22/2013 02/22/2013
 
004 (999) OTHER
THE ENTIRE APT 3F BEDROOMS AND LIVING ROOMCOM: NO ALL FAULT PROVIDED. 210.12
OPEN 02/22/2013 02/22/2013
 
005 (999) OTHER
THE ENTIRE APT, LIVINGROOM AND BEDROOMSCOM: NO A/C OUTLETS PROVIDED 210.52 (I)
OPEN 02/22/2013 02/22/2013
 
006 (999) OTHER
THE ENTIRE APT 3F BRANCH CIRCUIT WIRINGCOM: NOT GROUNDED. 250.146
OPEN 02/22/2013 02/22/2013
 
007 (999) OTHER
THIS IS NOT A FINAL INSPECTION. SEE THIS COMPLAINT #1343703
OPEN 02/22/2013 02/22/2013



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Plumb. Inspections  |  Electrical Inspection Work Order  |  Back