BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
Building Overview Work Items |
QUANTITY |
DESCRIPTION |
SERVICE SWITCHES |
|
A. Up to 100 AMPS |
0 |
|
B. 101 Up to 200 AMPS |
2 |
|
C. 201 Up to 600 AMPS |
0 |
|
D. 601 Up to 1200 AMPS |
0 |
|
E. Over 1200 AMPS |
0 |
|
SER. ENT. & FDR COND (EACH SET) |
|
A. Up to #2 CONDUCTOR |
0 |
|
B. Over #2 to 1/0 |
0 |
|
C. Over 1/0 to 250 MCM |
0 |
|
D. Over 250 MCM |
1 |
|
PANELS |
|
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
C. 3 Phase Up to 225 AMPS |
0 |
|
D. 3 Phase Over 225 AMPS |
0 |
|
ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
B. Each Additional 10 Floors Or Less |
0 |
|
BOILER CONTROLS |
0 |
|
OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
|
001 |
( 24) |
ARMORED CABLES ARE NOT PROPERLY SECURED KITCHEN: RL.OVEN AC CABLE NOT SUPPORTED..... - 320.30 |
RSLV |
06/06/2013 |
06/06/2013 |
06/26/2013 |
|
002 |
( 30) |
OUTLET BOXES ARE NOT SECURED 1FL: FLOOR RECEPTACLE BOX NOT SUPPORTED..... - 314.23 |
RSLV |
06/06/2013 |
06/06/2013 |
06/26/2013 |
|
003 |
(132) |
EQUIPMENT/MATERIAL IS NOT PROPERLY GROUNDED 1FL: EL.OVEN NO EQUIPMENT GND........ - 250.4A |
RSLV |
06/06/2013 |
06/06/2013 |
06/26/2013 |
|
004 |
( 42) |
BUSHINGS ARE MISSING OR LOOSE 1FL: EL.OVEN DISC SM BUSHING MISSING...... - 300.11,4G |
RSLV |
06/06/2013 |
06/06/2013 |
06/26/2013 |
|
005 |
( 34) |
KNOCKOUTS ARE NOT CLOSED IN PANEL BOX BSMT: 200A AND 100A SERV SW KO MISSING..... - 110.12A |
RSLV |
06/06/2013 |
06/06/2013 |
06/26/2013 |
|
006 |
( 1) |
SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER BSMT: 200A AND 100A SERV SW NOT BONDED/GROUNDED... - 250.92A |
RSLV |
06/06/2013 |
06/06/2013 |
06/26/2013 |
|
007 |
( 36) |
CONDUCTORS ARE NOT PROPERLY COLOR CODED BSMT: 200A COMBO COLOR CODE ON GND...... - 210.5 |
RSLV |
06/06/2013 |
06/06/2013 |
06/26/2013 |
|
008 |
(999) |
OTHER BSMT: TEMP WIRING NEUTRAL RUN SEPARATE FROM HOT LEG.. - 214.4B |
RSLV |
06/06/2013 |
06/06/2013 |
06/26/2013 |
|
009 |
( 7) |
EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT) BSMT: EMT NOT PROPERLY SUPPORTED..... - 358.30 |
RSLV |
06/06/2013 |
06/06/2013 |
06/26/2013 |
|
010 |
(999) |
OTHER BSMT: UNDERSIZE WATER MAIN FROM COLLECTIVE BAR.... - 250.66 |
RSLV |
06/06/2013 |
06/06/2013 |
06/26/2013 |
|
011 |
(356) |
RACEWAY LACKS MECHANICAL CONTINUITY BSMT: WATER RACEWAY NOT CONTINIOUS....... - 300.12 |
RSLV |
06/06/2013 |
06/06/2013 |
06/26/2013 |
|
012 |
(999) |
OTHER BSMT: LB FOR WATER MAIN NOT ACCESSIBLE.... - 110.26 |
RSLV |
06/06/2013 |
06/06/2013 |
06/26/2013 |
|
013 |
(999) |
OTHER BSMT: WALK-IN FREEZER LFMC NOT SUPPORTED... - 350 |
RSLV |
06/06/2013 |
06/06/2013 |
06/26/2013 |
|
014 |
( 37) |
MOTOR DISCONNECT SWITCH HAS NOT BEEN PROVIDED BSMT: WALK-IN FREEZR NO DISC SW FOR METER...... - 430.75 |
RSLV |
06/06/2013 |
06/06/2013 |
06/26/2013 |
|
015 |
(101) |
CONDUCTORS AND/OR EQUIPMENT USED IS NOT APPROVED 1FL: LIGHT FIXTURE NOT UL APPROVED...... - 110.2 |
RSLV |
06/06/2013 |
06/06/2013 |
06/26/2013 |
|
016 |
(132) |
EQUIPMENT/MATERIAL IS NOT PROPERLY GROUNDED OUTDOOR: A/C COMP NOT BONDED/GROUNDED....... - 250.4A |
RSLV |
06/06/2013 |
06/06/2013 |
06/26/2013 |
|
017 |
(311) |
FIXTURE NOT APPROVED FOR DAMP/WET LOCATION OUTDOOR: BY A/C COMP LIGHT FIXTURE NOT FOR WET/DAMP LOCATION- 410.10 |
RSLV |
06/06/2013 |
06/06/2013 |
06/26/2013 |
|
018 |
( 42) |
BUSHINGS ARE MISSING OR LOOSE OUTDOOR: A/C COMP DISC SWS BUSHING MISSING |
RSLV |
06/06/2013 |
06/06/2013 |
06/26/2013 |
|
019 |
( 6) |
FEEDER DIAGRAM DID NOT ACCOMPANY APPLICATION FOR INSPECTION BSMT: NO LOAD CALCULATION....... 215.5 |
RSLV |
06/06/2013 |
06/06/2013 |
06/26/2013 |
|
020 |
(109) |
SUFFICIENT WORK SPACE IS NOT PROVIDED/MAINTAINED BSMT: NO WORKING SPACE IN FRONT OF NEW METER...... - 110.26 |
RSLV |
06/06/2013 |
06/06/2013 |
06/26/2013 |