| BUILDING OVERVIEW |
Are Feeders Being Installed? : No |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 24) |
ARMORED CABLES ARE NOT PROPERLY SECURED 1ST FL: BEHIND THE FREEZERS BX CABLES HANGING |
RSLV |
07/16/2013 |
07/16/2013 |
11/27/2013 |
| |
| 002 |
(999) |
OTHER 1ST FL: BEHING THE COUNTERS GFCI NOT PROVIDED WITHIN 6FT OF BASIN210.8 |
RSLV |
07/16/2013 |
07/16/2013 |
11/27/2013 |
| |
| 003 |
( 56) |
ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED BSMT: 200 AMP PANEL MAIN LUGS NOT APPROVED |
RSLV |
07/16/2013 |
07/16/2013 |
11/27/2013 |
| |
| 004 |
( 29) |
OUTLET BOXES ARE NOT COVERED BSMT: CEILING 1900 BOX AND SPLICE BOX COVERS MISSING |
RSLV |
07/16/2013 |
07/16/2013 |
11/27/2013 |
| |
| 005 |
( 4) |
SERVICE IN EXCESS OF 1000KVA HAS NOT BEEN SUBMITTED FOR APPROVAL BMST: SERVICE OVER 1000 KVA AM 110.2 B,C |
RSLV |
11/27/2013 |
07/02/2014 |
09/11/2014 |
| |
| 006 |
(286) |
NO GFCI IN COMMERCIAL KITCHEN KITCHEN: NO GFCI PROTECTION PROVIDED (COMMERICAL) 210.8B2 |
RSLV |
11/27/2013 |
11/27/2013 |
07/02/2014 |
| |
| 007 |
( 29) |
OUTLET BOXES ARE NOT COVERED BSMT: OUTLET BOX(S) NOT COVERED 314.25 |
RSLV |
11/27/2013 |
11/27/2013 |
07/02/2014 |
| |
| 008 |
(255) |
NO FUSE COORDINATION EXISTS BSMT: NO FUSE COORDINATION AM 240.12A |
RSLV |
11/27/2013 |
07/02/2014 |
09/11/2014 |
| |
| 009 |
(999) |
OTHER BSMT: PANEL: MULTIWIRE CRS: NO SIMULT TRIP 210.4 |
RSLV |
11/27/2013 |
11/27/2013 |
07/02/2014 |
| |
| 010 |
(999) |
OTHER OUTDOOR: TEMP. 1200 A S DISC SW. NOT OPEN ON 90 110.26A2 |
RSLV |
11/27/2013 |
07/02/2014 |
09/11/2014 |
| |
| 011 |
(999) |
OTHER OUTDOOR: TEMP. SERVICE FEEDER OF 1000A 590.4B,2 |
RSLV |
11/27/2013 |
11/27/2013 |
07/02/2014 |