Electrical Application Details for App #: M336191
Premises: 235 WEST 4 STREET MANHATTAN BIN: 1078131     Block: 611   Lot: 2
   
Application Completed and Certified

Filed: 235 W 4 ST Census Tract:   73 Health Area:  6400
APT 4A & 5A Admin Area:   M - MANHATTAN Inspection Area:   R
NEW YORK, NY 10014 Community Board:   102
DOB Cross Street(s):   WEST 10 STREET,    CHARLES STREET
Status:   C - JOB IS SIGNED OFF 09/04/2013
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  01/24/2013 4:26 PM
Application Entered:   01/24/2013 Job Start Date:   01/25/2013
Last Change:   09/04/2013 Job End Date:   03/30/2013
Appointment Status:   
Last Inspection By:   BINGEL, LORI       On     07/17/2013      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 009984 Licensee Name: RICHARD A ALTMAN
Firm: 002468 Firm Name: COMPUTER AUTOMTD MACH LTD
Firm Phone: 212-924-0400  Firm Address: 94 EAST 4TH STREET DBA ALTMAN ELECTRIC NEW YORK NY 10003 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
T - TEMPORARY LIGHT & POWER
Total Fee:  $117.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: RICHARD RUBEL
Owner Business Name: CEDAR MANAGEMENT
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  3-PHASE 4-WIRE 100-AMP
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
004  4A  12             
005  5A  25  24  25             
Buildings Total 34  36  13  34                
Total Units : 120 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 06/12/2013
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  REPLACE 3-PHASE 4-WIRE PANEL

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M336191
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 06/04/2013 06/12/2013 LBI A (40) (9) Y
INSPECTION COMMENTS: *AC EQUIPMENT WAS NOT IN SCOPE OF WORK(4FL & ROOF)* **SEE OBJECTIONS
 
(2) 07/17/2013 07/25/2013 LBI C R (30) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M336191
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 46) PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY
4FL: 100A MAIN PANEL MISSING DIRECTORY..... - 408.4
RSLV 06/04/2013 06/04/2013 07/17/2013
 
002 (235) MAIN BREAKER NOT BOLTED IN
4FL: 100A BACKFED MAIN BREAKER NOT BOLTED...... - 408.36(D)
RSLV 06/04/2013 06/04/2013 07/17/2013
 
003 (272) EQUIPMENT GROUNDING CONDUCTOR NOT PROPERLY INSTALLED
4FL: 100A PANEL REQUIRES GND COND THRU FMC TO RISER SPLICE BOX- 408.40
RSLV 06/04/2013 06/04/2013 07/17/2013
 
004 (308) CONDUCTORS ARE NOT PROPERLY INSTALLED/TERMINATED
4FL: JUMPER TERMINATION OF STOVE & SUB-PANEL NEUTRAL IN 100A PANEL- AM 110.2
RSLV 06/04/2013 06/04/2013 07/17/2013
 
005 (272) EQUIPMENT GROUNDING CONDUCTOR NOT PROPERLY INSTALLED
4FL: STOVE EQUIPMENT GND TERM IN PANEL WITH TEK SCREW... - 250.8
RSLV 06/04/2013 06/04/2013 07/17/2013
 
006 ( 59) AFCI PROTECTION HAS NOT BEEN PROVIDED
4FL: HALL RECEPTACLES & LIGHT NOT A.F.C.I.PROTECTED... - 210.12(B)
RSLV 06/04/2013 06/04/2013 07/17/2013
 
007 (235) MAIN BREAKER NOT BOLTED IN
3FL: 60A BACKFED SUB-PANEL MAIN BREAKER NOT BOLTED.. - 408.36(D)
RSLV 06/04/2013 06/04/2013 07/17/2013
 
008 (999) OTHER
3FL: EATON A.F.C.I.BREAKER IN 60A SUBPANEL NOT COMBO TYPE- 210.12(B)
RSLV 06/04/2013 06/04/2013 07/17/2013
 
009 ( 46) PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY
3FL: 60A SUB-PANEL MISSING DIRECTORY....... - 408.4
RSLV 06/04/2013 06/04/2013 07/17/2013