| BUILDING OVERVIEW |
Are Feeders Being Installed? : No |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
1 |
3-PHASE 4-WIRE 100-AMP |
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 46) |
PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY 4FL: 100A MAIN PANEL MISSING DIRECTORY..... - 408.4 |
RSLV |
06/04/2013 |
06/04/2013 |
07/17/2013 |
| |
| 002 |
(235) |
MAIN BREAKER NOT BOLTED IN 4FL: 100A BACKFED MAIN BREAKER NOT BOLTED...... - 408.36(D) |
RSLV |
06/04/2013 |
06/04/2013 |
07/17/2013 |
| |
| 003 |
(272) |
EQUIPMENT GROUNDING CONDUCTOR NOT PROPERLY INSTALLED 4FL: 100A PANEL REQUIRES GND COND THRU FMC TO RISER SPLICE BOX- 408.40 |
RSLV |
06/04/2013 |
06/04/2013 |
07/17/2013 |
| |
| 004 |
(308) |
CONDUCTORS ARE NOT PROPERLY INSTALLED/TERMINATED 4FL: JUMPER TERMINATION OF STOVE & SUB-PANEL NEUTRAL IN 100A PANEL- AM 110.2 |
RSLV |
06/04/2013 |
06/04/2013 |
07/17/2013 |
| |
| 005 |
(272) |
EQUIPMENT GROUNDING CONDUCTOR NOT PROPERLY INSTALLED 4FL: STOVE EQUIPMENT GND TERM IN PANEL WITH TEK SCREW... - 250.8 |
RSLV |
06/04/2013 |
06/04/2013 |
07/17/2013 |
| |
| 006 |
( 59) |
AFCI PROTECTION HAS NOT BEEN PROVIDED 4FL: HALL RECEPTACLES & LIGHT NOT A.F.C.I.PROTECTED... - 210.12(B) |
RSLV |
06/04/2013 |
06/04/2013 |
07/17/2013 |
| |
| 007 |
(235) |
MAIN BREAKER NOT BOLTED IN 3FL: 60A BACKFED SUB-PANEL MAIN BREAKER NOT BOLTED.. - 408.36(D) |
RSLV |
06/04/2013 |
06/04/2013 |
07/17/2013 |
| |
| 008 |
(999) |
OTHER 3FL: EATON A.F.C.I.BREAKER IN 60A SUBPANEL NOT COMBO TYPE- 210.12(B) |
RSLV |
06/04/2013 |
06/04/2013 |
07/17/2013 |
| |
| 009 |
( 46) |
PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY 3FL: 60A SUB-PANEL MISSING DIRECTORY....... - 408.4 |
RSLV |
06/04/2013 |
06/04/2013 |
07/17/2013 |