| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
2 |
1 #400A 3 PH. 1 #600A 3PH |
| D. 601 Up to 1200 AMPS |
1 |
1 #800A 3 PHASE |
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
1 |
1#3/0THHN FOR FIRE PUMP |
| D. Over 250 MCM |
3 |
3 # 500MCM |
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
5 |
5#100A 20 CKT. |
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
3 |
3#200A 42 CKT. |
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 26) |
ARMORED CABLES ARE INSTALLED EXPOSED (ALL FLOORS) BX CABLE ARE INSTALLED EXPOSED T-OUT ART.320.15 |
OPEN |
06/24/2021 |
06/24/2021 |
|
| |
| 002 |
( 29) |
OUTLET BOXES ARE NOT COVERED (ALL FLOORS)BOXES MISSING COVERS CEILING BOX WIRES 3/0 STICK OUT FROM BOXART.314.25 |
OPEN |
06/24/2021 |
06/24/2021 |
|
| |
| 003 |
(999) |
OTHER (ALL FLOORS) APP NOT MATCH INSTALLATION |
OPEN |
06/24/2021 |
06/24/2021 |
|
| |
| 004 |
(999) |
OTHER (ALL FLOORS)APARTMENTS NOT INSPECTED NOT READY FOR INSPECTION , FIRE PUMPCONTROLLER NOT INSPECTED (NO ACCESS) COMPACTOR ROOM NOT INSPECTED(USED AS STORAGE) |
OPEN |
06/24/2021 |
06/24/2021 |
|
| |
| 005 |
( 1) |
SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER (CELLAR) SERVICE EQUIPMENT ENCLOSURE NOT BONDED TOGETHER ART.250.92A |
OPEN |
06/24/2021 |
06/24/2021 |
|
| |
| 006 |
(129) |
SERVICE SWITCH NEUTRAL NOT BONDED TO ENCLOSURE (CELLAR) SERVICE SWITCH NEUTRAL NOT BOUNDED TO ENCLOSURE ART 250.28 |
OPEN |
06/24/2021 |
06/24/2021 |
|
| |
| 007 |
(176) |
INSTALLATION DOES NOT MEET CODE REQUIREMENTS (CELLAR) SERVICE DETIORATING CONDITION ART.110.11 |
OPEN |
06/24/2021 |
06/24/2021 |
|
| |
| 008 |
(176) |
INSTALLATION DOES NOT MEET CODE REQUIREMENTS (CELLAR) LOAD CALCULATION FOR SERVICE ART. 220 |
OPEN |
06/24/2021 |
06/24/2021 |
|
| |
| 009 |
(176) |
INSTALLATION DOES NOT MEET CODE REQUIREMENTS (CELLAR) PANIC HARDWARE ELECTRICAL ROOM MISSING ART.110.26C3 |
OPEN |
06/24/2021 |
06/24/2021 |
|
| |
| 010 |
(176) |
INSTALLATION DOES NOT MEET CODE REQUIREMENTS (CELLAR) PANEL HANDLE TIES MISSING ART.210.4B |
OPEN |
06/24/2021 |
06/24/2021 |
|
| |
| 011 |
(176) |
INSTALLATION DOES NOT MEET CODE REQUIREMENTS (CELLAR) 400 AMP SERVICE SWITCH DIFFERENT FUSE ART.110.2 |
OPEN |
06/24/2021 |
06/24/2021 |
|
| |
| 012 |
(176) |
INSTALLATION DOES NOT MEET CODE REQUIREMENTS (CELLAR) ALL SERVICE DISCONNECT MUST BE IDENTIFIED ART. 230.70B |
OPEN |
06/24/2021 |
06/24/2021 |
|
| |
| 013 |
(192) |
CONDUCTORS ARE OVER FUSED AS PER TABLE 310.16 (CELLAR) PANEL WIRES OVER FUSED AS PER ART.310.16 |
OPEN |
06/24/2021 |
06/24/2021 |
|
| |
| 014 |
(225) |
OVERCURRENT PROTECTION IS NOT PROPERLY RATED, FIRE PUMP (CELLAR) OCP IS NOT PROPERLY RATED FIRE PUMP ART.AM 695.4B |
OPEN |
06/24/2021 |
06/24/2021 |
|
| |
| 015 |
(233) |
WATER CAN ENTER SERVICE EQUIPMENT (CELLAR) WATER CAN ENTER SERVICE EQUIPMENT ART.230.54 |
OPEN |
06/24/2021 |
06/24/2021 |
|
| |
| 016 |
(266) |
FIRE PUMP SERVICE SWITCH NOT PROPERLY IDENTIFIED (CELLAR)FIRE PUMP SERVICE SWITCH NOT PROPERLY IDENTIFIED ART.AM695.4B4 |
OPEN |
06/24/2021 |
06/24/2021 |
|
| |
| 017 |
(269) |
FIRE PUMP SUPPLY CONDUCTORS NOT PROPERLY INSTALLED (CELLAR)FIRE PUMP SUPPLY CONDUCTORS NOT PROPERLY INSTALLED ART. AM.695.6 |
OPEN |
06/24/2021 |
06/24/2021 |
|
| |
| 018 |
( 46) |
PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY (CELLAR) PANEL DIRECTORY MISSING ART.408.4 |
OPEN |
06/24/2021 |
06/24/2021 |
|