BIS Menu  |  After Hours Variance Permits  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M336105
Premises: 1528 1 AVENUE MANHATTAN BIN: 1050354     Block: 1559   Lot: 47
   
Application Completed and Certified

Filed: 400 E 80 ST Census Tract:   136 Health Area:  3800
FIRST AVENUE Admin Area:   M - MANHATTAN Inspection Area:   J
NEW YORK, NY 10075 Community Board:   108
DOB Cross Street(s):    1 AVENUE,    YORK AVENUE
Status:   C - JOB IS SIGNED OFF 01/17/2014
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  01/22/2013 8:40 PM
Application Entered:   01/22/2013 Job Start Date:   01/23/2013
Last Change:   01/17/2014 Job End Date:   01/23/2014
Appointment Status:   
Last Inspection By:   DALTON HENLON       On     05/31/2013      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011671 Licensee Name: ANGELO ARFANIS
Firm: 003576 Firm Name: FRACCAVENTO ELEC. CORP
Firm Phone: 718-621-9335  Firm Address: 2375 MCDONALD AVE BROOKLYN NY 11223 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $59.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: GEORGE GAILAS
Authorized Representative:  GEORGE GAILAS
Relationship To Owner:   OWNER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  1  1-12 CKT PANEL
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
002  2C    12             
Buildings Total   12                
Total Units : 26 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 04/05/2013
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M336105
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 03/27/2013 04/05/2013 EDB A (50) (2) Y
INSPECTION COMMENTS: **SEE OBJECTIONS
 
(2) 05/31/2013 06/11/2013 DAH C R (50) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M336105
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (340) RECEPTACLES NOT TAMPERPROOF
AP 2C: RECEPTACLE NOT TAMPER PROOF IN KITCHEN.... - 406.11
RSLV 03/27/2013 03/27/2013 05/31/2013
 
002 ( 63) RECEPTACLE OUTLETS NOT IN SUFFICIENT NUMBER
AP 2C: RECEPTACLE MISSING ON COUNTER TOP IN KITCHEN... - 210.52
RSLV 03/27/2013 03/27/2013 05/31/2013



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  After Hours Variance Permits  |  Electrical Inspection Work Order  |  Back