Premises: 655 5 AVENUE MANHATTAN BIN: 1035706     Block: 1288   Lot: 1
   
Application Completed and Certified

Filed: 1 E 52 ST Census Tract:   102 Health Area:  4800
ROOF Admin Area:   M - MANHATTAN Inspection Area:   L
NEW YORK, NY 10022 Community Board:   105
DOB Cross Street(s):    5 AVENUE,    MADISON AVENUE
Status:   C - JOB IS SIGNED OFF 08/09/2013
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  01/15/2013 2:06 PM
Application Entered:   01/15/2013 Job Start Date:   01/15/2013
Last Change:   08/09/2013 Job End Date:   04/15/2013
Appointment Status:   
Last Inspection By:   SOLAVNTO, THOMAS       On     08/02/2013      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010683 Licensee Name: DOMINICK STRIANO
Firm: 004045 Firm Name: STRIANO ELECTRIC CO., INC
Firm Phone: 718-225-2100  Firm Address: 160-29 UNION TURNPIKE FRESH MEADOWS NY 11366 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
3 - ELEVATOR/ESCALATOR/MATERIAL LIFT
Total Fee:  $425.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   O - Office Bldg
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: SALVATORE FERRAGAMO
Owner Business Name: SALVATORE FERRAGAMO
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  3  (1) 4 #250 MCM
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  2  (2) 25 HP
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 06/22/2013
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M335849
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 06/10/2013 06/22/2013 JKF A (75) (4) Y
INSPECTION COMMENTS: **SEE OBJECTIONS
 
(2) 08/02/2013 08/07/2013 TSO C R (20) (0) Y
INSPECTION COMMENTS: *RE: M334683 - ORIGINAL VIOLATION NOT DONE BY THIS CONTRACTOR*

OBJECTION FOR APPLICATION #: M335849
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 19) DEFECTIVE WIRING IS IN USE
ROOF: NO CONDUIT TO MOTOR HOUSING
RSLV 06/10/2013 06/10/2013 08/02/2013
 
002 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
ROOF: NO GROUNDING TO MOTOR
RSLV 06/10/2013 06/10/2013 08/02/2013
 
003 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
ROOF: MULTIPLE WIRES ON GND LUGS IN CONTROL PANELS
RSLV 06/10/2013 06/10/2013 08/02/2013
 
004 (191) LINE AND LOW VOLTAGE IN SAME RACEWAY FOR A/C UNITS
ROOF: MOTOR BRAKE WIRES AND MOTOR POWER
RSLV 06/10/2013 06/10/2013 08/02/2013