Electrical Application Details for App #: M335769
Premises: 113 ELIZABETH STREET MANHATTAN BIN: 1006932     Block: 470   Lot: 25
   
Application Completed and Certified

Filed: 113 ELIZABETH ST Census Tract:   41 Health Area:  6800
3A Admin Area:   M - MANHATTAN Inspection Area:   U
NEW YORK, NY 10013 Community Board:   102
DOB Cross Street(s):   GRAND STREET,    BROOME STREET
Status:   C - JOB IS SIGNED OFF 11/14/2013
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  01/12/2013 2:36 PM
Application Entered:   01/12/2013 Job Start Date:   01/12/2013
Last Change:   11/14/2013 Job End Date:   04/30/2013
Appointment Status:   
Last Inspection By:   RIVERA, F       On     09/26/2013      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011850 Licensee Name: JAMES P ST. JOHN
Firm: 003455 Firm Name: PATRIOT ELECTRIC CORP
Firm Phone: 718-736-8733  Firm Address: 15-17 126TH STREET 3RD FLOOR COLLEGE POINT NY 11356 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $60.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: JORDAN PLATT
Owner Business Name: KALED MANAGEMENT
Authorized Representative:  JORDAN PLATT
Relationship To Owner:   OWNERS REP


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  1  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
003    13               
Buildings Total 13                  
Total Units : 30 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 06/07/2013
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  APARTMENT RENOVATION NEW OUTLETS SWITCHES

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M335769
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 05/28/2013 06/07/2013 JKF V (50) (10) Y
INSPECTION COMMENTS: *PANEL O.C.P.D.NOT INSPECTED FOR FEEDER* **SEE OBJECTIONS
 
(2) 07/11/2013 07/19/2013 JKF Z (0) (0) Y
INSPECTION COMMENTS: NONE
 
(3) 09/26/2013 10/07/2013 FRI C R (20) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M335769
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
PANEL: HANDLE TIES...... - 210.4
RSLV 05/28/2013 05/28/2013 09/26/2013
 
002 (999) OTHER
KITCHEN: MICROWAVE BOX SET BACK...... - 314.20
RSLV 05/28/2013 05/28/2013 09/26/2013
 
003 ( 59) AFCI PROTECTION HAS NOT BEEN PROVIDED
PANEL: ALL GENERAL CIRCUITS
RSLV 05/28/2013 05/28/2013 09/26/2013
 
004 ( 35) APPROVED OUTLETS HAVE NOT BEEN PROVIDED FOR AIR CONDITIONERS
THROUGH-OUT
RSLV 05/28/2013 05/28/2013 09/26/2013
 
005 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
KITCHEN: DRYWALL SCREWS MICROWAVE RECEPTACLES
RSLV 05/28/2013 05/28/2013 09/26/2013
 
006 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
BATH: DRYWALL SCREWS WALL SCONCE
RSLV 05/28/2013 05/28/2013 09/26/2013
 
007 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
BATH: WALL SCONCE
RSLV 05/28/2013 05/28/2013 09/26/2013
 
008 ( 45) FIXTURE NOT INSTALLED IN AN APPROVED MANNER
BATH: WALL SCONCE
RSLV 05/28/2013 05/28/2013 09/26/2013
 
009 ( 53) GFCI HAS NOT BEEN PROVIDED
BATH: WALL SCONCE RECEPTACLE
RSLV 05/28/2013 05/28/2013 09/26/2013
 
010 ( 18) DEFECTIVE RECEPTACLES ARE IN USE
THROUGH-OUT: TAMPER RESISTANT NOT PROVIDED
RSLV 05/28/2013 05/28/2013 09/26/2013